Finishing, A. mantel and wall projections, B. facing material – Heatiator Heatilator Fireplace IDV4833IT User Manual

Page 43: Mantels mantel legs or wall projections

Advertising
background image

Heatilator • ICON DV-IDV Series • 4042-575 • Rev. S • 5/11

43

1 in. (25 mm) min.
to perpendicular wall

A

7.75 in. (159 mm) min.
from fireplace opening
to perpendicular wall

B

Mantel Leg or

Perpendicular Wall

Top of
Appliance

Drywall

A

B

Measured from top of fireplace opening (in inches)

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

11-1/2

12-1/4

13

13-3/4

14-1/2

15-1/4

16

16-3/4

17-1/2

18-1/4

19

19-3/4

20-1/2

21-1/4

22

22-3/4

30 in. minimum

to ceiling

1

2

10

10-3/4

14

14

Finishing

A. Mantel and Wall Projections

WARNING! Risk of Fire!

Comply with all minimum clear-

ances to combustibles as specifi ed. Framing or fi nishing
material closer than the minimums listed must be construct-
ed entirely of non-combustible materials (i.e., steel studs,
concrete board, etc).

Figure 14.1 Minimum Vertical and Maximum Horizontal Dimen-
sions

Figure 14.2 Mantel Leg or Wall Projections (Acceptable on both
sides of opening)

Mantels

Mantel Legs or Wall Projections

0 in.

0 in.

0 in.

Finish wall material may be combustible - Top and Sides

High Temperature Sealant (300° F/149° C min.)

Top and Side Seal Joint

A

B

Shaded area -
noncombustible
materials only

A

B

inches

44 3/8

46 1/2

mm

1127

1181

inches

48 7/8

60 1/2

mm

1241

1537

IDV4833

IDV6247

Model

B. Facing Material

• Metal front faces may be covered with non-combustible

materials only.

• Facing

and/or

fi nishing materials must not interfere with

air fl ow through louvers, operation of louvers or doors,
or access for service.

• Facing

and/or

fi nishing materials must never overhang

into the glass opening.

• Observe all clearances when applying combustible

materials.

• Seal joints between the fi nished wall and appliance top

and sides using a 300°F minimum sealant. Refer to
Figure 14.3.

WARNING! Risk of Fire! DO NOT apply combustible ma-
terials beyond the minimum clearances. Comply with all
minimum clearances to combustibles as specifi ed in this
manual. Overlapping materials could ignite and will inter-
fere with proper operation of doors and louvers.

Figure 14.3 Non-combustible Facing Diagram