Diagnostic Messages,

Continued

Diagnostic Messages,
continued

Table 32

Non-Critical Status Diagnostic Message Table, continued

SMV Status

SCT Status Message SFC Display Message TDC Status Message

Possible Cause

What to Do

9-6

Corrects Active on PV4

STATUS TAG ID.#

CORR. ACTIVE PV4

CORR. ACTIVE PV4

Calculated flow rate PV4 has been
calibrated.

Nothing – or do a reset corrects.

3-6

Density temperature or

pressure out of range

-

STATUS 3-6

Either the temperature (PV3) or the
pressure (PV2) is not within the
boundaries of SMV steam equation.

The SMV steam equation is defined
for pressures between 8 and 3000
psia, and temperature between
saturation and 1500

°

F, except

above 2000 psia.

Check to see if the PV
measurement is correct.

2-2

Excess Span Correct

PV1

Or

Span Correction is Out

of Limits

STATUS TAG ID.#

EX. SPAN COR PV1

EX. SPAN COR PV1

SPAN correction factor is outside
acceptable limits for PV1 range.
Could be that transmitter was in
input or output mode during a
CORRECT procedure.

Verify calibration.

If error persists, call the
Solutions Support Center

4-2

Excess Span Correct

PV2

STATUS TAG ID.#

EX. SPAN COR PV2

EX. SPAN COR PV2

SPAN correction factor is outside
acceptable limits for PV2 range.
Could be that transmitter was in
input or output mode during a
CORRECT procedure.

Verify calibration.

If error persists, call the
Solutions Support Center

8-2

Excess Span Correct

PV3

STATUS TAG ID.#

EX. SPAN COR PV3

EX. SPAN COR PV3

SPAN correction factor is outside
acceptable limits for PV3 range.

Verify calibration.

If error persists, call the
Solutions Support Center

9-2

Excess Span Correct

PV4

STATUS TAG ID.#

EX. SPAN COR PV4

EX. SPAN COR PV4

SPAN correction factor is outside
acceptable limits for PV4 range.

Verify calibration.

If error persists, call the
Solutions Support Center