8 tempconf configuration - pv3 – Honeywell SMV 3000 User Manual
Page 73
1/99
SMV 3000 Transmitter User’s Manual
61
6.8
TempConf Configuration - PV3
Engineering Units
The TempConf tab card displays the Low Range Value (LRV), Low Range
Limit (LRL), Upper Range Value (URV) and Upper Range Limit (URL)
for PV3 in the unit of measure selected in the Engineering Units field.
Selecting PV3
Engineering Units
Select one of the preprogrammed engineering units in Table 14 for display
of the PV3 measurements, depending upon output characterization
configuration.
Also select one of the preprogrammed engineering units for display of the
cold junction temperature readings (CJT Units field). This selection is
independent of the other sensor measurements. See Cold Junction
Compensation on next page.
Table 14
Pre-programmed Engineering Units for PV3
Engineering Unit
Meaning
C d
F
K
R
Degrees Celsius or Centigrade
Degrees Fahrenheit
Kelvin
Degrees Rankine
NOTE:
When output characterization configuration for PV3 is NON-LINEAR
(see Output Characterization), PV3 input readings are displayed in the
following units:
mV or V
Ohm
milliVolts or Volts (for Thermocouple sensor)
Ohms (for RTD sensor)
d Factory setting.
Continued on next page