SMV 3000 Transmitter User’s Manual

1/99

4.3

Piping SMV 3000 Transmitter,

Continued

Figure 12

Transmitter Location Below the Tap for Liquid or Steam
Flow Measurement

Low
Pressure
Connection

High
Pressure
Connection

To Low
Pressure
Connection

3-Valve
Manifold

To High

Pressure

Connection

ATTENTION

For liquid or steam, the piping should slope a minimum of 25.4 mm (1
inch) per 305 mm (1 foot). Slope the piping down towards the transmitter
if the transmitter is below the process connection so the bubbles may rise
back into the piping through the liquid. If the transmitter is located above
the process connection, the piping should rise vertically above the
transmitter; then slope down towards the flow line with a vent valve at the
high point. For gas measurement, use a condensate leg and drain at the
low point (freeze protection may be required here).

Continued on next page