2 connecting digital inputs and outputs, Connecting liebert environmental units, 1 connecting digital inputs – Liebert AC4 User Manual

Page 19: 2 connecting digital outputs, Connecting digital inputs and outputs, Connecting digital inputs, Connecting digital outputs, Caution

Advertising
background image

Wiring and Connections

13

3.2

Connecting Digital Inputs and Outputs

The digital inputs and outputs are found on the lower right side of the AC4’s printed wiring assembly

board. This section describes how to connect devices to the AC4’s inputs and outputs.
Each input is tied to an output with the same number:

• Input 1 is tied to Output 1 (default name: Device_1)
• Input 2 is tied to Output 2 (default name: Device_2)
• Input 3 is tied to Output 3 (default name: Device_3)
• Input 4 is tied to Output 4 (default name: Device_4)

Up to four devices may be connected to the AC4. Each device must be connected to an input and an

output with the same number.
To determine the proper wire size, see Table 4 - Wiring specifications.

Connecting Liebert Environmental Units

For Liebert environmental units, follow these steps (be sure to connect the same device to inputs and

outputs with the same number (Input 1 and Output 1, Input 2 and Output 2, and so on):

• Connect a digital input from the AC4 to the Common Alarm Relay of the environmental unit:

terminals 75/76 or TB1-6,TB1-7.

• Connect a digital output (numbered the same as the input) from the AC4 to the Remote Shutdown

(Power Control) of the environmental unit: terminal 37/38 or TB1-4, TB1-5.

3.2.1 Connecting Digital Inputs

The four digital inputs are found on the lower right side of

the AC4 just below the output terminal blocks, as shown at

right. These inputs are numbered 1 through 4.
To connect an input:
1. Turn OFF electrical power to the AC4.
2. If necessary, remove a conduit knockout to permit wire

entry into the AC4 enclosure.

3. Bring the wire(s) into the AC4 enclosure through a

conduit knockout or access slot.

4. Loosen the appropriate screw and slip the stripped end

of the wire into the terminal block.

5. Tighten the screw until it holds the wire snugly.

3.2.2 Connecting Digital Outputs

The four digital outputs are found on the lower right side of

the AC4 just above the input terminal blocks, as shown at

right. These outputs are numbered 1 through 4.
To connect an output:
1. Turn OFF electrical power to the AC4.
2. If necessary, remove a conduit knockout to permit wire entry into the AC4 enclosure.
3. Bring the wire(s) into the AC4 enclosure through a conduit knockout or access slot.
4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block.
5. Tighten the screw until it holds the wire snugly.

NOTE
Each terminal block is a removable assembly to permit easier connection of more than one

input or output at a time. If making multiple connections, grasp the upper portion of a block

and pull firmly until the assembly pulls apart.
After making the connections, push the removed piece back into the portion attached to the

printed wiring assembly until the terminal block pieces lock together.

!

CAUTION

To reduce the risk of fire or electric shock, do not interconnect the outputs of different class 2

circuits.

INPUT TERMINAL

BLOCKS

Note numbering keys

to right of terminal

blocks; inputs are

numbered from

bottom (1) to top (4)

OUTPUT TERMINAL

BLOCKS

Note numbering keys

to right of terminal

blocks; outputs are

numbered from

bottom (1) to top (4)

Numbering

keys

Advertising