System and Control Options

42

7.8

Setup Operation

The AC4’s operation features allow you to set up a rotation sequence to

alternate which devices are operating and which are placed on

Standby, as well as test devices while in Standby mode and specify

what to do when a Standby device goes into alarm as it is powered up.

You may also specify delay times after an output changes state, direct-

ing the AC4 to wait before acknowledging inputs or turning an output

on or off.
To change any operation features:

Log In and Choose Setup System

• From the Main Menu, use the arrows

↑↓

to

choose System and

Control, then press Enter

(see 7.1 - Login for help)

.

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑↓

to

choose

Setup System, then press Enter

.

Select Setup Operation

• From the Setup System Menu, shown at right, use the arrows

↑↓

to

choose Setup Operation and press Enter

.

• Use the steps following Table 18 to access any of the Setup Operation options.

Table 18 shows the default settings for operation options: automatic sequencing, standby testing,

failed standby, hold delay and restart.
Table 18

Default settings - operation features

Feature

Default

Other Options

AUTO SEQUENCING

OFF (Deactivated)

ON (Activated), 12h (Activated for 12-hour intervals)

STANDBY TESTING

OFF (Deactivated)

ON (Activated)

FAILED STANDBY

N (Deactivated)

Y (Activated)

HOLD DELAY

10:00 (No delay)

Any time (in minutes and seconds) from 00:00 to 99:59

RESTART

00:06 (No delay)

Any time (in minutes and seconds) from 00:00 to 99:59

Setup System Menu

SETUP INPUTS
SETUP COMMON ALARM
SETUP ZONES

↑↓

=NEXT

=SELECT

SETUP OUTPUTS
SETUP SYSTEM INFO

> SETUP OPERATION

Setup Operation Menu

> AUTO SEQUENCING OFF

STANDBY TESTING OFF
FAILED STANDBY

N

↑↓

=NEXT

=SELECT

HOLD DELAY : 10:00
RESTART

: 00:06