11

TI-131

0105

Model 700ERV

®

C L E A N • F R E S H • A I R

SPECIFICATIONS

LATENT RECOVERY (MOISTURE) TRANSFER CORES

Modular (2 section) enthalpic (moisture) transfer cores
arranged for efficient cross-flow ventilation.

MOTORS

Two PSC, 3 speed single shafted, 120 VAC, 2.75 Amps each
(5.5 total on high speed). HP - 1/10, 1625 RPM. Watts - total
on high speed - 648.

FILTERS

Washable air filters in exhaust and supply air streams.

BLOWERS

Centrifugal type rated at 700 CFM (329 L/s) free air delivery.
Each air stream has one single shafted motor driving a
centrifugal blower.

CONNECTION DUCT SIZES

Four - 14" x 8" (356 mm x 200 mm)

MOUNTING

Unit to be set on support brackets hung by threaded rod type
apparatus (brackets and rods not provided).

CASE

20 gauge prepainted galvanized steel (G60) for superior
corrosion resistance. Insulated with foil faced insulation
where required to prevent exterior condensation.

CONTROLS

Illuminated power switch, 3 speed blower control, low voltage
(24 VAC) terminals for connection of remote controls.

WEIGHT

142 lbs (64.4 kg)

SHIPPING WEIGHT

167 lbs. (75.8 kg)

OPTIONS

99-101

Sixty Minute Remote Timer

All units conform to CSA and UL standards.

WARRANTY

Units carry a 5 year warranty on the energy recovery cores
and 2 year replacement parts warranty.

ERVs are not recommended for regions where the design
temperature is below 25°F (-4°C)

AIRFLOWS (Each Air Stream)

423 (900)

378 (800)

329 (700)

282 (600)

235 (500)

190 (400)

143 (300)

94 (200)

42 (100)

AIRFLOW L/s (CFM)

25 (.1) 50 (.2) 75 (.3) 100 (.4) 125 (.5) 150 (.6) 175 (.7)

EXTERNAL STATIC PRESSURE IN PASCALS (IN. W.C.)

TOTAL CURRENT DRAW (AMPS) @ 120 VAC

5.5 HIGH

4.7 LOW

70%

60%

50%

143

(300)

190

(400)

235

(500)

282

(600)

329

(700)

TEMPERATURE EFFECTIVENESS

AIRFLOW IN L/s (CFM)

NOTE: Exhaust Relative Humidity (RH) at 40%

EFFECTIVENESS

HIGH SPEED

MED SPEED

LOW SPEED

5.0 MED

PERFORMANCE

29 5/8"

(753 mm)

8"

(200 mm)

FRONT VIEW

24 5/8 "

(625 mm)

28 3/4"

(730 mm)

14"

(356 mm)

8 1/4"

(210 mm)

INLET SIDE

DIMENSIONS 700ERV

inches (mm)

8"

(200 mm)

28 3/4"

(730 mm)

14"

(356 mm)

6 1/4"

(159 mm)

MOUNTING POINTS

CONTROLS

DISCHARGE SIDE

EXHAUST AIR

TO OUTSIDE

EXHAUST AIR

FROM BUILDING

SUPPLY AIR

TO BUILDING

SUPPLY AIR

FROM OUTSIDE

NOTE:
Service clearance
is 30 in. (760 mm)

HEAT RECOVERY VENTILATORS (HRVs)

¤

6 1/2"

(165 mm)

6 1/2"

(165 mm)

ENTHALPIC CORE

DATE: __________________________

PROJECT: ________________________________________

MECHANICAL CONTRACTOR: ________________________________

511 McCormick Blvd.

London, Ontario

N5W 4C8

Ph: (519) 457-1904
Fx: (519) 457-1676
Email: [email protected]
Website: www.lifebreath.com

Advertising
This manual is related to the following products: