TI-132

0105

Model 1200ERV

®

C L E A N • F R E S H • A I R

SPECIFICATIONS

LATENT RECOVERY (MOISTURE) TRANSFER CORES

Modular (3 section) latent recovery (moisture) transfer cores
arranged for efficient cross-flow ventilation.

MOTORS

Two PSC, 3 speed double shafted, 120 VAC, 4 Amps each
(8.1 total on high speed). HP - 1/4, 1625 RPM. Watts - total
on high speed - 972.

FILTERS

Washable air filters in exhaust and supply air streams.

BLOWERS

Centrifugal type rated at 1200 cfm (566 L/s) free air delivery.
Each air stream has one double shafted motor driving a
centrifugal blower.

CONNECTION DUCT SIZES

Four - 20" x 8" (508 mm x 200 mm).

MOUNTING

Unit to be set on support brackets hung by threaded rod type
apparatus. (brackets and rod not provided).

CASE

20 gauge prepainted galvanized steel (G60) for superior
corrosion resistance. Insulated with foil faced insulation
where required to prevent exterior condensation.

CONTROLS

Illuminated power switch, 3 speed blower control, low voltage
(24 VAC) terminals for connection of remote controls.

WEIGHT

191 lbs. (87 kg)

SHIPPING WEIGHT

215 lbs. (98 kg)

29 7/8"

(759 mm)

8"

(200 mm)

FRONT VIEW

24 5/8 "

(625 mm)

41 1/2"

(1055 mm)

20"

(508 mm)

6 3/4"

(172 mm)

INLET SIDE

DIMENSIONS 1200ERV

inches (mm)

8"

(200 mm)

41 1/2"

(1055 mm)

20"

(508 mm)

5 7/8"

(149 mm)

CONTROLS

DISCHARGE SIDE

EXHAUST AIR

TO OUTSIDE

EXHAUST AIR

FROM BUILDING

SUPPLY AIR

TO BUILDING

SUPPLY AIR

FROM OUTSIDE

NOTE:

Service clearance
is 30 in. (760 mm)
from front
access doors.

HEAT RECOVERY VENTILATORS (HRVs)

¤

10 3/8"

(263 mm)

10 3/8"

(263 mm)

ENTHALPIC CORE

OPTIONS

99-101

Sixty Minute Remote Timer

All units conform to CSA and UL standards.

WARRANTY

Units carry a 5 year warranty on the energy recovery cores
and 2 year replacement parts warranty.

ERVs are not recommended for regions where the design
temperature is below 25°F (-4°C)

AIRFLOWS (Each Air Stream)

613 (1300)

566 (1200)

518 (1100)

472 (1000)

423 (900)

378 (800)

329 (700)

282 (600)

235 (500)

AIRFLOW L/s (CFM)

25 (.1) 50 (.2) 75 (.3) 100 (.4) 125 (.5) 150 (.6) 175 (.7)

EXTERNAL STATIC PRESSURE IN PASCALS (in. W.C.)

TOTAL CURRENT DRAW (AMPS) @ 120 VAC

7.8 MED

8.1 HIGH

7.1 LOW

70%

60%

50%

235

(500)

282

(600)

329

(700)

TEMPERATURE EFFECTIVENESS

AIRFLOW IN L/s (CFM)

EFFECTIVENESS

HIGH SPEED

MED SPEED

LOW SPEED

378

(800)

423

(900)

472

(1000)

566

(1200)

518

(1100)

NOTE: Exhaust Relative Humidity (RH) at 40%

PERFORMANCE

DATE: __________________________

PROJECT: ________________________________________

MECHANICAL CONTRACTOR: ________________________________

511 McCormick Blvd.

London, Ontario

N5W 4C8

Ph: (519) 457-1904
Fx: (519) 457-1676
Email: [email protected]
Website: www.lifebreath.com

Advertising
This manual is related to the following products: