Model 700

FD/DD

SPECIFICATIONS

CORES

Modular (2 section) patented aluminum heat recovery cores
arranged for efficient cross-flow ventilation.

MOTORS

Two PSC, 3 speed single shafted, 120 VAC, 2.75 Amps each (5.5
total on high speed). HP - 1/10, 1625 RPM. Watts - total on high
speed - 648.

FILTERS

Washable air filters in exhaust and supply air streams.

BLOWERS

Centrifugal type rated at 329 L/s (700 CFM) free air delivery. Each
air stream has one single shafted motor driving a centrifugal blower.

CONNECTION DUCT SIZES

Four - 356 mm x 200 mm (14" x 8" ).

MOUNTING

Unit to be set on support brackets hung by threaded rod type
apparatus (brackets and rods not provided).

CASE

20 gauge prepainted galvanized steel (G60) for superior corrosion
resistance. Insulated with foil faced insulation where required to
prevent exterior condensation. Drain connections; two - 12 mm
(1/2") O.D.

CONTROLS

Illuminated power switch, 3 speed blower control, low voltage (24
VAC) terminals for connection of remote controls and defrost light
indicating automatic operation.

DEFROST CONTROLS

MODEL 700 FD - Interrupts supply air while exhaust air defrosts core.
MODEL 700DD - Supply bypass routes indoor air to defrost core.

WEIGHT

64.4 kg (142 lbs.)

SHIPPING WEIGHT

75.8 kg (167 lbs.)

TI-103

0011

AIRFLOWS (Each Air Stream)

MODEL 700FD, 700DD

423 (900)

378 (800)

329 (700)

282 (600)

235 (500)

190 (400)

143 (300)

94 (200)

42 (100)

AIRFLOW L/s (CFM)

25 (.1) 50 (.2) 75 (.3) 100 (.4) 125 (.5) 150 (.6) 175 (.7)

EXTERNAL STATIC PRESSURE IN PASCALS (IN. W.C.)

TOTAL CURRENT DRAW (AMPS) @ 120 VAC

5.5 HIGH

4.7 LOW

70%

60%

50%

143

(300)

190

(400)

235

(500)

282

(600)

329

(700)

TEMPERATURE EFFECTIVENESS

AIRFLOW IN L/s (CFM)

NOTE: Exhaust Relative Humidity (RH) at 40%

EFFECTIVENESS

HIGH SPEED

MED SPEED

LOW SPEED

5.0 MED

PERFORMANCE

753 mm (29 5/8")

200 mm

(8")

FRONT VIEW

625 mm

(24 5/8 ")

730 mm

(28 3/4")

356 mm

(14")

210 mm

(8 1/4")

INLET SIDE

DRAIN CONNECTION

DIMENSIONS 700

mm (inches)

200 mm

(8")

730 mm

(28 3/4")

356 mm

(14")

159 mm

(6 1/4")

MOUNTING POINTS

CONTROLS

DISCHARGE SIDE

EXHAUST AIR

TO OUTSIDE

EXHAUST AIR

FROM BUILDING

SUPPLY AIR

TO BUILDING

SUPPLY AIR

FROM OUTSIDE

NOTE:
Service clearance
is 760 mm (30 in.)
from front
access doors

HEAT RECOVERY VENTILATORS (HRVs)

¤

DD MODEL ONLY

FD MODEL ONLY

165 mm

(6 1/2")

165 mm

(6 1/2")

OPTIONS

99-101

Sixty Minute Timer

99-130

Remote Wall Mount Dehumidistat Control
24 VAC only

All units conform to CSA and UL standards.

WARRANTY

All units carry a 15 year warranty on the heat recovery cores
and a 2 year replacement parts warranty.

DATE: __________________________

PROJECT: ________________________________________

MECHANICAL CONTRACTOR: ________________________________

511 McCormick Blvd.

London, Ontario

N5W 4C8

Ph: (519) 457-1904
Fx: (519) 457-1676
Email: [email protected]
Website: www.lifebreath.com

Advertising
This manual is related to the following products: