4.2.2

LCD Touch Screen Calibration

A touch screen calibration page may be evoked from the user interface default operating screen:

Perform a diagonal action or "swipe" from the top right area of the LCD to the bottom left area:

Figure 4–Begin LCD touch screen calibration (default operating screen)

When the calibration screen appears, tap on the center of the first target within 20 seconds to complete this step:

Figure 5– LCD touch screen calibration screen target one

Tap on the center of the second target (bottom right area of the screen) to complete the calibration:

Figure 6– LCD touch screen calibration screen target two

NOTE: Both the targets must be tapped correctly for the calibration to take effect. This is done to prevent the calibration

from changing dramatically from the default.

Calibration will be ignored if the user does

not tap in the general area of the target

(correct area is the size of the target icon)

If the user does not tap in the general area

of the first target, then calibration will not

be saved no matter what happens in the

second target

Count down timer; calibration will be
ignored when time runs out

Count down timer; calibration will be
ignored when time runs out

Tap on the center of the second target
and calibration will be saved
automatically

Tap on the center of the first target

(top left area of the screen)

CAUTION: Do not use a pen, pencil or

other sharp object to tap on the CXC

screen. This will scratch the screen and

may void the warranty.