Wiring and Set Up

3-2610-31 to 8900 Set Up

1. Connect the 8058, 2610-31, and 8900 as shown in the diagram.
2. Press and hold ENTER key for 5 seconds.
3. The display should fl ash “System Setup”.
4. Press ENTER key.
5. Scroll to the desired channel for Dissolved

Oxygen.

6. Press

the

► key.

7. Enter the password.
8. Repeatedly press the ▼ key until the lower

line of the display reads “Other (4-20)”.

9. Press ENTER key.
10. The 8900 will warn that “Channel Data will

be Reset. Are you sure?” Press the ▼ key
so that “Yes” is fl ashing and press ENTER
key.

11. Simultaneously press the▲ and ▼ keys to

return to the Menu Directory.

12. Press the ▼ key to select the “Channel

Settings” menu and press ENTER key to
select.

13. Use the ▼ key to select the channel used

in step 5.

14. Press the ► key to change the label and press ENTER when done.
15. Press the ▼ key to select the

abbreviation.

16. Press the ► key to change the

label and press ENTER when
done. Press the ▼ key to select
the Units.

17. Press the ► key to change

the Units. The 2610 shipped
with default units of mg/L or
ppm, either can be used. Press
ENTER when completed.

18. Press the ▼ key to select the 4

mA Set Point.

19. Press the ► key to change the set point. By default the 4 mA set point for the 2610 is 0.0. Press the ENTER

key when complete.

20. Press the ▼ key to select the 20 mA Set Point.
21. Press the ► key to change the set point. By default the 20 mA set point for the 2610 is 20.0. Press the

ENTER key when complete.

22. Press the ▼ key to select the Decimal location.
23. Press the ► key and change the decimal position if desired. Press ENTER when complete.
24. Simultaneously press the ▲ and ▼ keys to exit out of the channel menu.
25. Continue programming other options in the 8900 or simultaneously press the ▲ and ▼ keys to return to the

View Mode.

6

7

8

9

10

11

12

13

14

+

-

3 2 1

6 5 4

7 8 9

Loop1

PWR

N/C

S L

DATA

3

Loop2

PWR

+GF+ SIGNET

8058-2

BLACK (5 VDC)

BLACK

BLACK

BLACK

RED

RED

WHITE (GND)

RED (S

3

L)

24 VDC

Regulated

Power Supply

DO Sensor 1

3-2610-31

No connection

DO Sensor 2

3-2610-31

No connection

8900 Sensor Inputs

BROWN

BROWN

RED

DO Sensor

3-2610-31

24 VDC

Regulated

Power Supply

BLACK

Input

4-20 mA

Output

S

3

L

SHIELD

(no connection)

Signet 8058 i-Go™

4-20 mA to S

3

L Converter

+GF+

4-20 mA input S

3

L Output

V–

V+

BROWN

GREEN

BLUE

WHITE

No connection

8058-1

8900 Sensor Inputs

6

7

8

9

10

11

12

13

14

BLACK

RED

WHITE

SHIELD

(no connection)

Wiring and Set Up

Advertising