Technical data

General data and operating conditions

4

l

18

LDCDS−EL100 EN 9.0

4

Technical data

4.1

General data and operating conditions

Conformity and approval

Conformity

CE

EN 61000−6−1 (−3),
VDE 0839−6−1 (−3)

2002 residential area

EN 61000−6−2 (−4),
VDE 0839−6−2 (−4)

2006 industrial premises

EN 55022

EN 55024

Equipment of information technology

Approbation

UL

UL 508
CSA C22.2

Programmable Controllers (File−No. E236341)

Other

RoHS

Products lead−free in accordance with CE Directive
2011/65/EU

Protection of persons and equipment

Safety

VDE0805 (EN60950),
VDE0870, UL

Type of protection

IP65 (front) / IP20 (back)
Type 1, 2 and 5 enclosure

Class of protection

3

Ambient conditions

Climatic

Temperature

Storage/Transport

0 ... +60 °C

Operation

EL 1xx ECO
EL 1xx CAN/MPI

0 ... +50 °C

EL 1xx ECO PLC
EL 1xx PLC

5 ... +45 °C

Relative humidity

10 ... 90 %, no condensation

Site altitude

Storage/Transport

< 12.000 m amsl

Operation

< 3.000 m amsl

Vibration test according to EN 61131−2 (programmable controllers)

Vibration

EN 60068−2−6

1 g

Shock

EN 60068−2−27

15 g

Mounting conditions

Mounting place

Control cabinet door

Mounting position

Terminals at the bottom