Electrical installation

Wiring
EL 1xx CAN/PLC/MPI

6

l

30

LDCDS−EL100 EN 9.0

6.3

Wiring

6.3.1

EL 1xx CAN/PLC/MPI

Mains connection

)

Note!

ƒ

Observe the max. permissible input voltage.
Professionally fuse the device on the input side against voltage fluctuations
and voltage peaks.

ƒ

The HMI boots up as soon as the supply voltage is applied.
After the operating system has been shut down, the HMI switches off
automatically. For restarting, the supply voltage has to be disconnected for a
short time.

EL100−005

Description

Connection type

Cable type

0V

U

DC 24 V connection

3−pole Phoenix Combicon

socket

Cable (conductor

cross−section max. 2.5 mm

2

)

with Phoenix Combicon plug,

MSTB 2.5 / 3−STF−5.08

IPC001

PE connection

Threaded bolt M4

Separate earthing conductor

(min. 2.5 mm

2

) with ring

cable lug

IPC001