Operation – Lenze HMI for visualisation / with control technology User Manual
Page 52
Operation
Control Panel Applets
CAN Gateway
l
52
LDCDS−EL100 EN 9.0
"State" register
EL100−032
Gateway: Start and stop gateway function
Bus state: Current state of the CAN system bus (BUS−ON or BUS−OFF)
Bus load (%): Current bus load
Error state: Current error
Client connections: Number of connected Ethernet nodes
Status message interpretation (bus state and error state):
BUS−ON and OK: CAN communication is alright.
BUS−ON and ERROR: The warning limit of the CAN controller has been reached or exceeded
(too many error frames). CAN communication is still possible.
BUS−OFF and ERROR: The CAN controller has reached the BUS−OFF state. CAN
communication is not possible. A reset of the device is required.
"Ethernet" register
EL100−033
Adapter name: Select the adapter here whose settings are to be displayed.
MAC address, IP address, Subnet mask: Settings from the "Network and Dial−up
Connections for Ethernet" applet.