Danger – Viking Pump TSM750: M10 Power Load Monitor User Manual

Page 4

Advertising
background image

DANGER !

Terminals 1 and 2 (s1, s2) carry line voltage.

TABLE 1

Current Transformer And Number Of Primary Windings

1. Check the rated motor current on the motor plate.

2. Compare this value with the Rated Motor Current in

table 1.

3. From table 1, select the appropriate numbers of

windings for the current transformer.

EXAMPLE

• Rated motor current = 12 A.

• Select 10. 1 - 12. 5 from the first column in table 1 and

choose 2-E90-013-999-00 with two (2) primary windings.

Note!

Maximum length of CTM cable is 39 inches (1 m).

Note!

Normally the appropriate current transformer will have

been ordered and shipped with the Power Load Monitor,

check that this is the case; contact the supplier if in doubt.

FIGURE 5

Example 1 And 3 Windings.

Note!

The transformer connection and orientation are not polarity

sensitive.

CURRENT TRANSFORMERS

VIKING PART

NUMBER

2-E90-012-999-00 2-E90-013-999-00 2-E90-014-999-00

TRANSFORMER

MODEL

CTM010

CTM025

CTM050

RATED MOTOR

CURRENT (A)

0.40-1.00

10

1.01– 2.00

5

2.01–3.00

3

3.1-5.0

2

5.1-10.0

1

10.1-12.5

2

12.6-25.0

1

26-50

1

CURRENT TRANSFORMER SELECTION

FOR MOTORS UP TO 50 A

FIGURE 4

Example: CTM O25 With 2 Windings For 12 A Motor

SECTION TSM 750

ISSUE A

PAGE 3 OF 7