Caution – Viking Pump TSM750: M10 Power Load Monitor User Manual

Page 6

Advertising
background image

PARAMETER

VALUE

FACTORY

SETTING

NOTE

RATED POWER

0 1 2 4 8 16 32 64

64

See Table 3

RELAY INVERTED

0(no) 1(yes)

0

0=Relay Activated

alarm

ALARM CURRENT= 0

0(no) 1(yes)

0

Alarm at no motor

current

MAX OR MIN

0(MIN) 1(MAX)

1

0=underload

1=overload

RESPONSE DELAY

0 1 2 4 8 16 32 64

2

Response delay in

seconds (0=50ms)

START DELAY

0 1 2 4 8 16 32 64

2

Start delay in seconds

MARGIN

(% of rated power)

0 1 2 4 8 16 32 64

8

Load change for alarm

sensitivity. Fig 6

AUTO SET

Autoset load level

is automatically set

if VAL key is

pressed for 3

seconds

VAL key must be

pressed when LED

parameter AUTOSET

is lit. LED bar is

switched off when

Autoset level is set.

SETTING

RATED MOTOR POWER IN HP

OR Kw

0

0 – 0.5

1

0.51 - 1.5

2

1.51 - 2.5

4

2.51 - 6

8

6.1 - 12

16

12.1 - 24

32

24.1 - 48

64

48.1 - 75

FIGURE 6

Alarm Level and Margin

Hints!

Change the load on the machine to find out if

appropriate load limit margin is set correctly. You can

also reduce the margin by one or more steps to find

out at what level the machine will trip. See figure 6.

Set/Reset e.g. start delay, response delay, trip margin

etc. if necessary (see table 2).

If the alarm level is difficult to set - simply perform an

Auto Set when the motor is stopped. Then start the

machine, run at normal load and perform an Auto Set

again.

If a wrong value is unintentionally set - simply set a

new value. If the value is not confirmed by pressing

PAR, the new value is not accepted (time out after 30

seconds

).

SECTION TSM 750

ISSUE A

PAGE 5 OF 7

Pump with overload protection, motor 11 kW (fig. 6).

1. Check output power on motor plate and see table 3

(11 kW =Rated Motor Power 6.1- 12) -setting 8.

2. Switch on the supply voltage - Power LED green.

3. Press

PAR once - “LED” AUTO SET turns green.

4. Keep pressing

PAR until RATED POWER is

selected.

5. Press

VAL - Value “64” flashes (factory setting).

6. Set recommended value according to table 3. Keep

pressing

VAL until chosen value (8) flashes.

7. Confirm chosen value by pressing

PAR.

8. Press

PAR again and select MAX.

9. Press

VAL . Choose the factory setting MAX -

Overload Protection – “1”.

10. Confirm chosen value (1) by pressing

PAR.

11. Press

PAR again and select RELAY INVERTED.

12. Press

VAL. Choose the factory setting “no” =“0”.

13. Confirm chosen value (0) by pressing

PAR.

The above parameters are necessary to set for safe

functioning. Note that “Rated Power” for the motor must be

set before Auto Set.

EXAMPLE: PUMP WITH OVERLOAD

PROTECTION

CAUTION!

Positive displacement pumps require some form of

over-pressure protection to be placed in the discharge

line in conjunction with the Power Load Monitor.

Pressure spikes created by sudden discharge line

blockage may cause serious pump damage.

TABLE 2

Parameters and Values

TABLE 3

Setting or Rated Motor Power

Alarm Level

(overload monitor)

Power at AUTO SET

(Auto set load level)

Alarm Level

(underload monitor)

POWER

Overload

(MAX)

Margin

Margin

t

VIKING PUMP, INC.

● A Unit of IDEX Corporation ●

Cedar Falls, IA 50613 USA ©2002

SECTION TSM 750

ISSUE

B

PAGE 6 OF 8