Caution, Programming operation, Operation – Viking Pump TSM750: M10 Power Load Monitor User Manual

Page 5

Advertising
background image

pressing PAR.

CAUTION!

Make sure that all safety measures have been

taken before switching on the supply voltage and

starting the motor/ machine in order to avoid

personal injury.

Verify that suction and discharge lines are

connected and tight, valves are open and liquid is

flowing under normal conditions to the pump before

beginning to set the Power Load Monitor for normal

operating conditions.

1. Switch on the supply voltage - Power LED turns

green.

2. Press

PAR once - “LED” AUTO SET turns green.

3. Keep pressing

PAR until the desired parameter is

selected e. g. RATED POWER, see table 2 and 3.

4. Press

VAL - Factory set value or earlier set value

flashes e. g. “64”.

5. Keep pressing

VAL until desired value is displayed

(0 - 64).

6. Confirm chosen value by pressing

PAR.

7. Press

PAR again and repeat steps 3 to 6 for all

parameters except for AUTO SET. See tables 2, 3

and fig. 6 for possible value setting for each of the

eight parameters.

8. Start and run motor/system at normal load conditions,

also wait until the START DELAY has expired.

Hint!

Short-circuit the output relay during the set-up, this

prevents the equipment from stopping unintentionally, see

Caution! in section “Wiring”.

9. Press

PAR once - “LED” AUTO SET turns green.

10. Press and hold

VAL for 3 seconds, at normal

machine load. The Auto Set load level is

automatically set and the LED is switched off.

11.

Set/re-set e.g. start delay, response delay, margin

etc. if necessary (see table 2, 3, and figure 6).

PROGRAMMING

OPERATION

LED

• A constant green LED indicates a parameter type.

• A flashing green LED indicates a value.

Under normal system operation, the eight LED's are all

off (see table 2). Any LED's illuminated will be

automatically switched off 30 seconds after the last

key press.

AUTO SET

The alarm load level is automatically set by the Auto

Set function (see Programming). The value for a

parameter, e.g. seconds, kW, HP or margin, can only

be set as 0, 1, 2, 4, 8, 16, 32 or 64. Select closest

value.

PAR

Parameter

change (LED

light constant

green) -pressing

PAR key when

parameter is

displayed

VAL

Value setting -

Pressing VAL

key when green

LED is flashing

increases value. A

changed value is

confirmed by

pressing PAR.

Reset Input

Terminal 5 and 6 are

used for external reset

and selection of

latched/unlatched alarm.

Relay Output

Terminal 6, 7 and

8 output relay.

Motor Terminals

Terminal 9 (L1), 11 (L2), and 13 (L3)

for supply and motor voltage input.

Current Input

Terminal 1 and 2. Current

Transformer; CTM 010,

025, or 050 (Max 50 A

motor).

Power/ Alarm

The Power/ Alarm

LED indicates

green at "power

on" and at normal

load. Red at

alarm.

Reset

Reset a latched alarm by

pressing both PAR and VAL at

the same time for 3 seconds.

OPERATION

Set up the monitor as below:

SECTION TSM 750

ISSUE A

PAGE 4 OF 7

SET- UP AND FIRST START

VIKING PUMP, INC. ● A Unit of IDEX Corporation ●

Cedar Falls, IA 50613 USA ©2002

SECTION TSM 750

ISSUE

B

PAGE 5 OF 8