Maintenance

7-20

Automation System S7-400 Hardware and Installation

A5E00850741-01

You can replace an interface submodule with another one without having to remove
the associated CPU from the rack. Follow the steps outlined below:

1. Switch the CPU to STOP (not the synchronization module of a redundant

system).

2. Switch off the power supply (not the synchronization module of a redundant

system).

3. Loosen the screws of the sub-D-connector and remove all connectors.
4. Loosen the two captive slot-head screws which secure the front plate of the

interface submodule to the left frame of the card slot so that the screws can be

removed by 6 mm.

5. Carefully remove the interface submodule from the guide support of the card

slot (see figure 7-1). Hold the interface module on the long sides of the front

plate.

Guide

rails

Figure 7-1

Inserting an Interface Submodule in a CPU

Installing Interface Submodules

In order to install an interface submodule, proceed in reverse order. For further
information, see section 6.10 ”Installing Interface Submodules”.