Siemens Automation System S7-400 User Manual

Page 170

Advertising
background image

Assembling and Installing Systems

A-2

Automation System S7-400 Hardware and Installation

A5E00850741-01

A.1

General Rules and Regulations for Operating
the S7-400

General Basic Rules

On account of the many possible applications of the S7-400, this chapter can only
cover the basic rules for the electrical configuration. You must at least comply with
these basic rules to ensure fault-free operation of the S7-400.

Specific Application

Observe the safety and accident prevention regulations applying to specific
applications, for example, the Machine Protection Guidelines.

EMERGENCY OFF Devices

EMERGENCY OFF devices complying with IEC 60204-1 (which corresponds to
VDE 0113-1) must remain effective in all operating modes of the plant or system.

Reactions of the Plant after Certain Events

The following table shows how you must respond to the reactions of a plant to
certain events.

Event

Requirement

Failure of the operating or

supply voltage of the S7-400

Hazardous operating states must not occur.

Tripping of the Emergency

Off device

Hazardous operating states must not occur.

Restoration of the operating

or supply voltage of the

S7-400

Hazardous operating states must not occur. No

uncontrolled or undefined restart of the system must occur.

Restart after release of the

Emergency Off device

Hazardous operating states must not occur. No

uncontrolled or undefined restart of the system must occur.