Assembling and Installing Systems

A-7

Automation System S7-400 Hardware and Installation

A5E00850741-01

Five Basic Rules for Ensuring Electromagnetic Compatibility

In many cases, you can ensure electromagnetic compatibility by observing the
following five basic rules:

Rule 1: Large Area Grounding

When installing the programmable controllers, provide large-area good quality
grounding of the inactive metal parts (see Section A.3).

• Make a large-area low-impedance connection of all inactive metal parts to

chassis ground.

• For screw connections on painted or anodized metal parts, either use special

contact washers or remove the insulating protective layers from the contact

points.

• If possible, do not use aluminum parts for grounding. Aluminum oxidizes easily

and is therefore less suitable for grounding.

• Make a central connection between chassis ground and the ground/protective

ground conductor system.

Rule 2: Correct Cable Routing

Ensure proper routing of lines when wiring (see Sections A.7 and A.8).

• Arrange the cabling in line groups (AC power cables, power supply cables,

signal lines, data lines).

• Always install AC power cables and signal or data lines in separate ducts or

bunches.

• Route the signal and data lines as closely as possible to grounded surfaces

such as cabinet elements, metal bars and cabinet panels.

Rule 3: Secure Cable Shields

Ensure that cable shields are properly secured (see Section 4.9).

• Only use shielded data lines. The shield must have a large-area connection to

ground at each end.

• Analog lines must always be shielded. For the transfer of signals with low

amplitudes, it may be advisable to connect the shield to ground at only one end.

• Provide the line shields with a large-area connection to a shield/protective

ground bar immediately after the cabinet inlet, and secure the shields with cable

clamps. Route the grounded shield as far as the module without interruption, but

do not ground it there again.

• There must be a low-impedance connection between shield/protective ground

bar and cabinet/housing.

• Use metal or metallized connector cases for shielded data lines.