Manual – Weil-McLain PLUS LINE PLUS-E017-A/1206 User Manual

Page 23

Advertising
background image

Part Number PLUS-E017-A/1206

2

Manual

• Installation • Start-Up • Usage • Maintenance • Parts

Figure 10

Recirculation connection at water heater

Figure 9

Recirculation components

Components

1 Circulator — Little flow is required to maintain a temperature in the piping. Size of

circulator depends on minimum flow requirements of the tempering valve. Minimum
flow rates of the tempering valve must be maintained.

2 Aquastat — Used to control the on-off position of the circulator. Aquastat is set 5° to

10° lower than mixed water outlet of the mixing valve (#7). The circulator cannot run
continuously as bypass through the mixing valve will eventually allow the temperature
on the piping to climb to the water heater temperature during draw periods.

3 – 6  Check valves — Assure the flow of water in one direction. Each check valve func-

tions as follows: #3 and #4 prevent bypass in the event of pressure drop, #5 prevents
thermal siphoning of hot water to the cold water supply, #6 prevents flow of cold water
to the tempered water supply. A draw of tempered water will not result in flow of cold
water into the return loop.

Operation

During period of normal use (fixtures on) — Circulator is off. There is no flow through
#6, there is flow through #5 equal to the flow at the fixtures, there is flow through #3
and/or #4 equal to flow at fixture.

When all fixtures are off — Circulator is off. There is no flow through #3, #4, #5 or #6.
Water temperature in piping is cooling.

When temperature at aquastat #2 falls 10° below temperature to be maintained
— Circulator is on. There is flow through #6 equal to the minimum required by the
mixing valve, flow through #3 and #4 equals the flow of the circulator. There is no flow
through #5.

Aquastat reaches temperature — Circulator is off. There is no flow through #3, #4, #5
or #6.

Problems

Missing check valves #3 or #4 — Extreme pressure drop can cause reverse flow of
water; hot to cold supply or cold to hot supply.

Missing check valve #5 — Hot water can migrate from the water heater back through
the cold water supply.

Missing check valve #6 — Cold water can be forced back through the tempered water
supply when a fixture is opened.

No aquastat #2 — Pump runs continuously. Small amount of water will pass through
mixing valve. Eventually all hot water is flowing through valve. Recirculated water
through cold port, hot water through hot port.

Circulator too small — Mixing valve performance erratic.

Advertising