Field wiring — gas boilers only, Manual, Wiring a system circulator – Weil-McLain PLUS LINE PLUS-E017-A/1206 User Manual

Page 31: Routing line voltage wiring, Low voltage connections, Room thermostat, Outdoor temperature sensor, Water heater thermostat, Additional limits

Advertising
background image

Part Number PLUS-E017-A/1206

1

Manual

• Installation • Start-Up • Usage • Maintenance • Parts

Wiring a system circulator

1. For combined systems, to activate a system circu-

lator when the Boiler circulator operates, wire as

shown at bottom of Figure 1, page 0.

2. You must install a relay as shown. DO NOT wire in

parallel with the Boiler circulator. See

CAUTION

in

Figure 1.

Routing line voltage wiring

1. Route line voltage connections to the jacket open-

ings shown in Figure 18.

Low voltage connections

(Fig. 18)

1. Connect low voltage wiring to low voltage termi-

nal strip (Figure 19, page 2, item 1) as shown in

Figure 19 and the boiler wiring diagram.

2. Route all low voltage wires through grommeted

jacket opening to right of low voltage terminal strip,

as shown in Figure 18.

Room thermostat

(space heating)

1. For combined space heating/water heating systems,

connect Figure 19, item 2, room thermostat or end

switch (isolated contact only) between terminals 
and .

2. Install thermostat on inside wall away from influ-

ences of drafts, hot or cold water pipes, lighting

fixtures, television, sunrays, or fireplaces.

. Thermostat anticipator (if applicable):

a. If connected directly to boiler, set for 0.1 amps.
b. If connected to relays or other devices, set to match

total electrical power requirements of connected
devices. See device manufacturers’ specifications and
thermostat instructions for details.

Outdoor temperature sensor

1. Outdoor reset operation applies only to combined

space heating/water heating systems.

2. Connect outdoor temperature sensor (Figure 19,

item ) between terminals 1 and 2 to enable out-

door reset operation of the

Gasboiler. If

fixed-temperature operation is required, do not

install outdoor sensor.

. Mount sensor on exterior wall, shielded from di-

rect sunlight or flow of heat or cooling from other

sources.

. Install a summer/winter switch (Figure 19, item )

across terminals 1 and 2 to force fixed-temperature

operation during summer months. (When the

switch is closed, boiler will attempt to maintain

constant temperature.)

. Route sensor wires through the grommeted hole at

right of the electrical entrance (see Figure 18).

Water heater thermostat

1. Connect PLUS water heater aquastat terminals

“C” and “1” to

Gas boiler low voltage ter-

minal strip between terminals  and  (Figure 9,

item ).

Additional limits

1. Connect additional limit controls and interlocks

between the terminals shown in Figure 19.

2. Controls connected between terminals  and 

(see Figure 19, item ) will cause a soft lockout

(automatic reset). When limit(s) closes, boiler will

resume normal operation.

. Controls connected between terminals  and 8

(see Figure 19, item ). will cause a hard lockout

(manual reset). The boiler will only restart after

the Ultra display panel RESET switch is pressed.

Figure 18

Routing field wiring

Field wiring —

Gas boilers only

(continued)

B3

Gas