Table 3

Combined space heating/water
heating (see Notes)

Table 4

Dedicated water-heating, using circulator
supplied with boiler (see Notes)

Boiler PLUS

Model

1st Hour

rating, GPH

Boiler

piping

Head losses, Feet w.c.

DHW

Pump

115°F

140°F GPM Rec.

size

Boiler Heater Piping TOTAL

Ultra-

80

40

160

124

6.6

1"

5.8

1.0

2.4

9.2

007

60

168

132

80

176

140

100

190

155

110

210

175

119

230

190

Ultra-

105

40

203

141

6.4

1"

5.9

1.0

2.3

9.3

007

60

211

162

80

219

170

100

230

185

110

250

205

119

270

225

Ultra-

155

40

238

153

8.7

1"

5.7

1.0

3.9

10.6

0010

60

294

190

9.6

1¼"

7.1

1.0

2.3

10.5

80

302

230

10.8

1¼"

9.0

1.0

2.8

12.8

0012

100

315

245

110

335

265

119

355

285

Ultra-

230

40

248

160

12.0

1¼"

8.2

1.0

3.4

12.6

0012

60

330

196

80

411

305

13.5

1¼" 10.0

1.0

4.2

15.2

0014

100

440

335

110

460

355

119

480

375

Ultra-

310

40

254

164

15.0

1¼"

6.0

1.0

5.1

12.1

0012

60

351

208

18.6

1½"

8.5

1.0

3.3

12.8

0011

80

579

373

22.0

1½" 11.2

1.0

4.5

16.6

0013

100

440

335

110

460

355

119

480

375

1. First hour ratings in Tables  and  are based

on:

• 11°F or 10°F domestic outlet water supply

temperature from water heater.

• 0°F domestic water inlet temperature.
• 190°F boiler water temperature leaving

Gas boiler.

• Circulator and pipe sizes as given in the

Tables.

2. If the net Btu/hr rating of the boiler is close to

the space heating load (for combined systems)

— or if there is an unusually large demand for

domestic water — increased boiler capacity

may be required.

Boiler PLUS

Model

1st Hour

rating, GPH

Boiler

piping

Head losses, Feet w.c.

Circ.

115°F 140°F GPM

Rec.

size

Boiler Heater Piping TOTAL

Ultra-

80

40

160

124

6.6

1"

5.8

1.0

2.4

9.2

007

60

168

132

80

176

140

100

190

155

110

210

175

119

230

190

Ultra-

105

40

203

141

6.4

1"

5.9

1.0

2.3

9.2

007

60

211

162

80

219

170

100

230

185

110

250

205

119

270

225

Ultra-

155

40

250

160

12.1

1¼”

11.4

1.0

4.5

16.9

0014

60

295

220

80

305

230

100

315

245

110

335

265

119

355

285

Ultra-

230

40

240

170

13.5

1¼”

10.0

1.0

5.2

16.2

0014

60

335

220

80

430

325

100

440

335

110

460

355

119

480

375

Ultra-

310

40

240

170

18.3

1½”

8.3

1.0

4.2

13.5

0014

60

335

220

80

580

410

100

590

435

110

610

465

119

630

485

Notes

Tables

3 and 4

Figure 16

Pump curves for Taco circulators

Gas

The following ratings are for Ultra Gas boilers only, with supply water temperature at 190°F.

For boilers other than Ultra Gas, see page  for ratings.