1.6 AF-300 G11 Drive Ratings Efficiency and Watts Loss
HP
Rating
Rated Output
Current (A)
Rated Output
Power (KVA)
Efficiency at 2KHz
(%)
Efficiency at
15KHz (%)
Watts Loss at
2KHz (W)
Watts Loss at
15KHz (W)
Internal DB
(W)
230VAC
0.25
1.5
0.59
92.0
90.5
25
30
10
0.5
3
1.1
93.5
91.7
35
45
10
1
5
1.9
94.9
94.0
50
60
10
2
8
3.1
95.7
94.1
80
110
30
3
11
4.3
95.9
94.9
110
140
30
5
17
6.7
96.2
95.4
170
210
30
7.5
25
9.9
96.2
95.2
240
310
60
10
33
13
96.5
95.3
300
415
60
15
46
18
96.4
95.2
450
620
N/A
20
59
23
96.9
95.9
540
720
N/A
25
74
29
96.8
95.8
670
890
N/A
30
87
34
96.5
95.5
880
1160
N/A
40
115
45
97.2
96.5
950
1200
N/A
50
145
57
97.2
96.4
1200
1550
N/A
60
180
71
97.3
96.6
1400
1750
N/A
75
215
85
97.4
96.8
1600
2050
N/A
2KHz (%)
10KHz (%)
2KHz (W)
10KHz (W)
100
283
112
97.4
97.0
2150
2500
N/A
125
346
137
97.4
97.0
2600
3000
N/A
460VAC
0.5
1.5
1.1
93.5
89.3
35
60
10
1
2.5
1.9
95.4
91.7
45
85
10
2
3.7
2.9
96.7
94.1
60
110
30
3
5.5
4.3
97.0
94.5
80
150
30
5
9
7.1
97.1
95.0
130
230
30
7.5
13
10
97.3
95.3
170
300
60
10
18
14
97.3
95.4
230
400
60
15
24
19
97.6
95.9
300
520
N/A
20
30
23
97.9
96.5
360
610
N/A
25
39
31
97.8
96.4
460
770
N/A
30
45
35
97.8
96.4
550
900
N/A
40
60
47
97.8
96.4
750
1250
N/A
50
75
59
97.7
96.1
950
1650
N/A
60
91
72
97.8
96.4
1100
1850
N/A
75
112
89
97.9
96.5
1300
2200
N/A
2KHz (%)
10KHz (%)
2KHz (W)
10KHz (W)
100
150
119
98.1
97.2
1550
2350
N/A
125
176
140
98.0
97.2
1950
2800
N/A
150
210
167
98.0
97.3
2400
3350
N/A
200
253
202
98.2
97.3
2650
3900
N/A
250
304
242
98.1
97.3
3250
4700
N/A
300
377
300
98.2
97.4
3900
5750
N/A
350
415
330
98.2
97.4
4350
6300
N/A
400
520
414
98.2
97.4
5450
7950
N/A
450
585
466
98.2
97.4
6150
8950
N/A
500
650
518
98.3
97.4
6700
9950
N/A
600
740
590
98.2
97.4
7750