P:motor parameters, H:high performance functions – GE Industrial Solutions AF-300 G11 User Manual
Page 56
5-3
Data subject to change without notice 7/07. © 2007 GE Drives
Func.
Factory Setting
Data
Change
No.
Setting Range
Unit
Min.
30 HP
40 HP
Format
during op
C20
JOG frequency
C20
JOG Hz
0.00 to 400.00 Hz
Hz
0.01
5.00
5
Y
C21
PATTERN
(mode select)
C21
PATTERN
0,1,2
-
-
0
1
operation
C22
(Stage 1)
C22
STAGE 1
Operation time: 0.00 to 6000 s
s
0.01
0.00 F1
13
C23
(Stage 2)
C23
STAGE 2
F1 to F4 and R1 to R4
0.00 F1
13
C24
(Stage 3)
C24
STAGE 3
0.00 F1
13
C25
(Stage 4)
C25
STAGE 4
0.00 F1
13
C26
(Stage 5)
C26
STAGE 5
0.00 F1
13
C27
(Stage 6)
C27
STAGE 6
0.00 F1
13
C28
(Stage 7)
C28
STAGE 7
0.00 F1
13
C30
Frequency command 2
C30
FREQ CMD 2
0 to 11
-
-
2
1
N
C31
Offset adjust
(terminal [12])
C31
BIAS 12
-100.0 to +100.0%
%
0.1
0.0
4
Y
C32
(terminal [C1])
C32
GAIN 12
0.0 to +200.0%
%
0.1
100.0
3
Y
5-31
C33
Analog setting signal filter
C33
REF FILTER
0.00 to 5.00s
s
0.01
0.05
5
Y
P:Motor Parameters
P01
Number of motor 1 poles
P01
M1 POLES
2 to 14
-
2
4
9
N
P02
Motor 1
(capacity)
P02
M1-CAP
Up to 30 HP: 0.01 to 60 HP
Hp
0.01
motor capacity
5
40 HP and above: 0.01 to 600 HP
P03
(rated current)
P03
M1-Ir
0.00 to 2000 A
A
0.01
motor rated current
19
N
P04
(tuning)
P04
M1 TUN1
0, 1, 2
-
-
0
21
N
P05
(on-line tuning)
P05
M1 TUN2
0, 1
-
-
0
1
N
P06
(no-load current)
P06
M1-Io
0.00 to 2000 A
A
0.01
standard rated value
19
N
P07
(%R1 setting)
P07
M1-%R1
0.00 to 50.00%
%
0.01
standard rated value
5
Y
P08
(%X setting)
P08
M1-%X
0.00 to 50.00%
%
0.01
standard rated value
5
Y
P09
Slip compensation control
P09
SLIP COMP1
0.00 to 15.00 Hz
Hz
0.01
0.00
5
Y
H:High Performance Functions
H03
Data initializing
H03
DATA INIT
0, 1
-
-
0
1
N
H04
Auto-reset
(times)
H04
AUTO-RESET
0, 1 to 10 times
-
1
0
1
Y
H05
(reset interval)
H05
RESET INT
2 to 20 s
s
1
5
1
Y
H06
Fan stop operation
H06
FAN STOP
0, 1
-
-
0
1
Y
H07
ACC/DEC pattern (mode select)
H07
ACC PTN
0,1,2,3
-
-
0
1
N
H08
Rev. phase sequence lock
H08
REV LOCK
0, 1
-
-
0
1
N
H09
Start mode
H09
START MODE
0, 1, 2
-
--
0
1
N
H10
Energy-saving operation
H10
ENERGY SAV
0, 1
-
-
0
1
Y
H11
DEC mode
H11
DEC MODE
0, 1
-
-
0
1
Y
H12
Instantaneous OC limiting
H12
INST CL
0, 1
-
-
1
1
N
H13
Auto-restart
(restart time)
H13
RESTART t
0.1 to 10.0 s
s
0.1
0.1
0.5
3
N
H14
(freq. fall rate)
H14
FALL RATE
0.00 to 100.00 Hz/s
Hz/s
0.01
10.00
5
H15
(holding DC voltage)
H15
HOLD V
3-phase, 230V class: 200 to 300V
V
1
200V class: 235V
1
3-phase, 460V class: 400 to 600V
400V class: 470V
H16
(OPR command self hold time)
H16
SELFHOLD t
0.0 to 30.0 s, 999
s
0.1
999
3
H18
Torque control
H18
TRQ CTRL
0, 1, 2
-
-
0
1
H19
Active drive
H19
AUT RED
0, 1
-
-
0
1
Y
H20
PID control
(mode select)
H20
PID MODE
0, 1, 2
--
-
0
1
N
5-38
H21
(feedback signal)
H21
FB SIGNAL
0, 1, 2, 3
-
-
1
1
N
H22
(P-gain)
H22
P-GAIN
0.01 to 10.00 times
-
0.01
0.1
5
Y
H23
(I-gain)
H23
I-GAIN
0.0, 0.1 to 3600 s
s
0.1
0.0
3
Y
H24
(D-gain)
H24
D-GAIN
0.00 s , 0.01 to 10.0 s
s
0.01
0.00
5
Y
H25
(feedback filter)
H25
FB FILTER
0.0 to 60.0 s
s
0.1
0.5
3
Y
H26
PTC thermistor
(mode select)
H26
PTC MODE
0, 1
0
1
Y
H27
(level)
H27
PTC LEVEL
0.00 to 5.00V
V
0.01
1.60
5
Y
H28
Droop operation
H28
DROOP
9.9 to 0.0 Hz
Hz
0.1
0.0
4
Y
H30
Serial link
(function select)
H30
LINK FUNC
0, 1, 2, 3
-
-
0
1
Y
H31
Modbus-RTU
(address)
H31
ADDRESS
0 (broadcast), 1 to 247
-
1
1
1
N
H32
(mode select on no response error)
H32
MODE ON ER
0, 1, 2, 3
-
-
0
1
Y
H33
(timer)
H33
TIMER
0.0 to 60.0 s
s
-
2.0
3
Y
H34
(baud rate)
H34
BAUD RATE
0, 1, 2, 3
-
-
1
1
Y
H35
(data length)
H35
LENGTH
0 (8-bit fixed)
-
-
0
1
Y
H36
(parity check)
H36
PARITY
0, 1, 2
-
-
0
1
Y
H37
(stop bits)
H37
STOP BITS
0 (2-bit), 1(1-bit)
-
-
0
1
Y
H38
(no response error detection time)
H38
NO RES t
0 (no detection), 1 to 60 s
s
1
0
1
Y
H39
(response interval)
H39
INTERVAL
0.00 to 1.00 s
s
0.01
0.01
5
Y
5-42
5-43
5-37
5-39/40
5-41
5-36
Pg.
5-29
5-29/30
5-30
5-32
5-33
5-34
5-35
Y
N
Y
Name
LCD Display
N
N