Brooks, Model 5850i – Brooks Instrument 5850i User Manual

Page 10

Advertising
background image

1-4

Brooks

®

Model 5850i

Section 1 Introduction

Installation and Operation Manual

X-TMF-5850i-MFC-eng

Part Number: 541B108AAG

December, 2008

Temperature Sensitivity

Zero: Less than ±0.075% full scale per degree C.

Span: Less than ±1.0% full scale shift over 10-50°C range.

Mounting Attitude Sensitivity

±0.5% maximum full scale deviation after re-zeroing.

Command Input

Jumper Selectable: 0-5 Vdc, Input resistance 200k ohm or 4-20 mAdc,

Input resistance 75 ohm.

Leak Integrity

1 x 10

-9

Atm. scc/sec Helium

Control Range

50 to 1

Mechanical Connection

Interchangeable with most popular mass flow controllers.

Refer to Figure 2-1.

Electrical Connections

D-type, 15-pin connector (DA-15P). Mating connector supplied.

*Standard temperature and pressure in accordance with SEMI
(Semiconductor Equipment and Materials International) standard: 0°C and
101.3 kPa (760 Torr). The mass flow controller can be calibrated to other
reference standard conditions. Specify at time of ordering.