Diagnostic menu parameter table (factory page), Test – Watlow Series F4S/D User Manual
Page 118
1 0 . 4
■
D i a g n o s t i c s
Wa t l o w S e r i e s F 4 S / D
✔ NOTE: For more information about how parameter settings
affect the controller’s operation, see the Features Chapter.
Diagnostic Menu Parameter Table (Factory Page)
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
[I/O, Set, Ch]
Parameters to Appear
Active: Always.
1602 w
Default all values?
Yes (800)
Full Defaults
Causes all parame-
ters and profile val-
ues to revert to
their factory default
settings.
Active: Always.
1513 w
Yes (1)
Display Test
Checks LED display
segments by turning
them on and off.
Active: Always.
✔NOTE: Must be in the Calibra-
tion or Test Menu at the display
for this prompt to work via com-
munications.
1514 w
All Off
(0)
Output 1A
(1)
Output 1B
(2)
Output 2A
(3)
Output 2B
(4)
Retransmit 1
(5)
Retransmit 2
(6)
Alarm 1
(7)
Alarm 2
(8)
Digital Out 1
(9)
Digital Out 2
(10)
Digital Out 3
(11)
Digital Out 4
(12)
Digital Out 5
(13)
Digital Out 6
(14)
Digital Out 7
(15)
Digital Out 8
(16)
All On
(17)
Communications (18)
Test Outputs
Choose output to
test.
Main > Factory > Test
Test