Alarms, Alarm set points, Alarm hysteresis – Watlow Series F4S/D User Manual

Page 72: Process or deviation alarms

Advertising
background image

6 . 8

F e a t u r e s

Wa t l o w S e r i e s F 4 S / D

Alarms

Alarms are activated when the process value or

temperature leaves a defined range. A user can

configure how and when an alarm is triggered,

what action it takes and whether it turns off auto-

matically when the alarm condition is over.
Configure alarm outputs in the Setup Page before

setting alarm set points.

Alarm Set Points

The alarm high set point defines the process value

or temperature that will trigger a high side alarm.

It must be higher than the alarm low set point and

lower than the high limit of the sensor range.
The alarm low set point defines the temperature

that will trigger a low side alarm. It must be lower

than the alarm high set point and higher than the

low limit of the sensor range.
Location in software: Operations Page > Alarm Set

Point > Alarm x (1 or 2).

Alarm Hysteresis

An alarm state is triggered when the process value

reaches the alarm high or alarm low set point.

Alarm hysteresis defines how far the process must

return into the normal operating range before the

alarm can be cleared.
Alarm hysteresis is a zone inside each alarm set

point. This zone is defined by adding the hysteresis

value to the alarm low set point or subtracting the

hysteresis value from the alarm high set point.
Location in software: Setup Page > Alarm Output x

(1 or 2).

Figure 6.8 — Alarm Settings.

Normal Operating Range

Low Side Alarm Range

High Side Alarm Range

Alarm High Set Point

Alarm Low Set Point

Time

Temperature

Alarm Hysteresis

Alarm Hysteresis

Process or Deviation Alarms

A process alarm uses one or two absolute set points

to define an alarm condition. A deviation alarm us-

es one or two set points that are defined relative to

the control set point. High and low alarm set points

are calculated by adding and/or subtracting offset

values from the control set point. If the set point

changes, the window defined by the alarm set

points automatically changes with it.
In the Series F4 you must configure each alarm

output as either a process or deviation alarm.
Location in software: Setup Page > Alarm Output x

(1 or 2).

Advertising