Setup Page Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

(I/O, Set, Ch)

Parameters to Appear

NOTE:
Press the Information Key

ˆ for more task-related tips.

Setup Page Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

[I/O, Set, Ch]

Parameters to Appear

Active: Always.

Output

710

[1]

727

[2]

r/w

Low end of

sensor

range

-19999 to high scale -1

(minimum sensor

range) (-19999 to

High Scale -1)

Low Scale

Set low end of cur-

rent or voltage

range to retransmit.

Active: Always.

Output

836

[1]

837

[2]

r/w

4 to 20mA (0)

4 to 20mA (0)

0 to 20mA (1)

0 to 5V (2)

1 to 5V (3)

0 to 10V (4)

Analog Range

Select voltage or

current range to

retransmit.

Active: Always. (Values appear

only if the source is enabled.)

Output

709

[1]

726

[2]

r/w

Input 1 (0)

Input 1 (0)

Input 2 (1)

Input 3 (2)

Set Point 1 (3)

Set Point 2 (4)

Channel 1 Power (5)

Channel 2 Power (6)

Retransmit Source

Choose a source for

retransmit signal.

Main > Setup > Retransmit Output x (1 and 2)

Retransmit Output x (1 and 2)

Active if Alarm Output is en-

abled.

Output

708

[1]

725

[2]

r/w

Yes on Main

Page (0)

Yes on Main Page (0)

No (1)

Alarm Messages

Select the alarm

message option.

Active if Alarm Output is

enabled.

Output

707

[1]

724

[2]

Open on

Alarm (0)

Open on Alarm (0)

Close on Alarm (1)

Alarm Logic

Select the alarm

logic option.

Active if Alarm Output is

enabled.

Output

706

[1]

723

[2]

r/w

Both (0)

Both (0)

Low (1)

High (2)

Alarm Sides

Choose to enable

Low, High or both

alarm set points.

Active if Alarm Output is

enabled.

Output

703

[1]

720

[2]

r/w

3 (3)

1 to 30000

(1 to 30000)

Alarm Hysteresis

Set the alarm

hysteresis.

Active if Alarm Output is

enabled.

Output

705

[1]

722

[2]

r/w

No (0)

No (0)

Yes (1)

Silencing

Choose whether to

mask alarms on

power-up.

Active if Alarm Output is

enabled.

Output

704

[1]

721

[2]

r/w

Alarm Self-

Clears (0)

Alarm Self-Clears (0)

Alarm Latches (1)

Latching

Choose automatic or

manual clearing of

alarms.

Active if the source is

enabled.

Output

716

[1]

733

[2]

r/w

Off (0)

Input 1 (0)

Input 2 (1)

Input 3 (2)

Alarm Source

Select the alarm

source.

Active always.

Output

702

[1]

719

[2]

r/w

Off (0)

Off (0)

Process (1)

Deviation (2)

Alarm Type

Select the alarm

type.

Active always.

3200-3209

3210-3219

r/w

ALARMX

<selected by user>

(ASCII Values)

Name

Name the alarm for

easy reference.

Main > Setup > Alarm Output x (1 and 2)

Alarm Output x (1 and 2)