Hardware specifications (main unit) – Yokogawa Touch Screen GP20 User Manual

Page 430

Advertising
background image

5

<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2012-2013, Yokogawa Electric Corporation

GS 04L52B01-01EN

May. 7, 2013-00

HARDWARE SPECIFICATIONS

(MAIN UNIT)

Display

Display unit*:

GP10: 5.7-inch TFT color LCD (640 × 480 dots)

GP20: 12.1-inch TFT color LCD (800 × 600 dots)

*

A small number of missing or steady-on LCD

pixels and minor variations in brightness

uniformity is a normal display characteristic and

not a malfunction.

Touch screen:

4 wire resistive touch screen

Construction

• Material;

Case: Metal plate

Bezel and display cover: Polycarbonate

• Color;

Case: Smoke blue

Bezel: Charcoal grey light

• External dimensions:

When installing modules

GP10: 144(W) × 168(H) × 248(D) mm

GP20: 288(W) × 318(H) × 248(D) mm

When uninstalling modules

GP10: 144(W) × 168(H) × 197(D) mm

GP20: 288(W) × 318(H) × 197(D) mm

(D: depth from the panel mounting plane)

• Weight:

GP10: Approx. 1.9 kg, GP20: Approx. 5.7 kg

(excluding modules)

Power Supply

• Rated supply voltage: 100 to 240 VAC

• Allowable power supply voltage range: 90 to 132,

180 to 264 VAC

• Rated power supply frequency: 50/60 Hz

• Power consumption:

Supply

voltage

LCD backlight

off

Normal

operation

Maximum

100 V AC

GP10: 16 VA

GP20: 28 VA

GP10: 20 VA

GP20: 34 VA

GP10: 48 VA

GP20: 90 VA

240 V AC

GP10: 24 VA

GP20: 38 VA

GP10: 30 VA

GP20: 45 VA

GP10: 60 VA

GP20: 110 VA

* The following combinations are assumed for LCD

backlight off and normal operation.

GP10: 1 AI module, 1 DO module, 1 DI module

GP20: 5 AI modules, 4 DO modules, 1 DI module

• Module power supply voltage: The total allowable

power consumption of respective modules is up

to 6 W in the GP10 and up to 20 W in the GP20.

• Allowable interruption time: Less than 1 cycle of

the power supply frequency

Isolation

• Insulation resistance: Between the Ethernet,

RS-422/485, and each insulation terminals and

earth: 20 MΩ or greater at 500 VDC

• Withstand voltage:

Between the power terminal and earth: 3000 V

AC at 50/60 Hz for one minute

Between the contact output terminal and earth:

3000 VAC at 50/60 Hz for one minute

Between the input/output modules and earth:

Depends on the specification of I/O module.

• Ground; Grounding resistance: 100 Ω or less

• Isolation:

Power terminal

The circuits divided by lines are insulated mutually.

Internal circuit

FAIL output terminal
Ethernet port
RS-422/485 terminal
Input and output module terminal

Input and output module internal circuit
Earth (PE) terminal
RS-232 terminal
SD card slot
USB port

Safety and EMC Standards

• CSA: CSA22.2 No.61010.1, installation

category II (*1), and pollution degree 2 (*2), and

CSA-C22.2 NO. 61010-2-030-12

• UL: UL61010-1, UL 61010-2-030 (CSA NRTL/C)

• CE:

EMC directive

EN61326-1 compliance, Class A Table 2

EN61000-3-2 compliance

EN61000-3-3 compliance

EN55011 Class A Group 1

Low voltage directive

EN61010-1, EN 61010-2-030

Installation category II (*1)

Pollution degree 2 (*2)

Measurement category II (*3)

• C-Tick: EN55011 compliance, Class A Group 1

• KC marking: Electromagnetic wave interference

prevention standard, electromagnetic wave

protection standard compliance

*1 Installation category (overvoltage category) II:

Describes a number which defines a transient

overvoltage condition.

Implies the regulation for impulse withstand

voltage.

“II” applies to electrical equipment which

is supplied from the fixed installation like a

distribution board.

*2 Pollution degree 2:

Describes the degree to which a solid, liquid,

or gas which deteriorates dielectric strength or

surface resistivity is adhering.

“2” applies to normal indoor atmosphere.

Normally, only non-conductive pollution occurs.

*3 Measurement category: Depends on the

specification of each modules

Advertising
This manual is related to the following products: