Setting the Operation Mode of a Module

Path

GX/GP:

MENU key > Browse tab > Setting > Setting menu Measurement settings >

Module settings

Select module > Module 0 to 9

1

Web browser:

Config. tab > Measurement settings > Module settings

Hardware configurator:

Measurement settings > Module settings

1 The module numbers that appear depend on the GX/GP module configuration.

Description

AI Modules

Operation mode

Setup Item

Selectable Range or Options

Default Value

Operation mode

*2

2ch Only, Low noise mode; 10ch Normal mode

10ch Normal mode

*2 Fixed to 10ch mode if an electromagnetic relay scanner type (Type suffix code: -T1) analog

input module is in use.

Operation mode

Set the operation mode to use. For details on the operation modes, see the explanation.

DI Modules

Operation mode

Setup Item

Selectable Range or Options

Default Value

Operation mode

Remote, Normal

Normal

Operation mode

Set the operation mode to use. For details on the operation modes, see the explanation.

Explanation

2ch Mode and 10ch Mode (AI modules)

In 10ch mode, measurement is possible on CH1 to CH10.

In 2ch mode, measurement is possible only on CH1 and CH2. (CH3 to CH10 are fixed to

Skip.)

In 10ch mode, when the scan interval is set to 100 ms or 200 ms, the A/D integration time

is fixed at 1.67 ms. This prevents power frequency noise from being eliminated, causing

measured values to wobble (especially for temperature).

In 2ch mode, when the scan interval is 100 ms or 200 ms, the A/D integration time is

16.67 ms or 20 ms. This allows power frequency noise to be eliminated.

Note that the selectable A/D integration times vary depending on the 2ch/10ch mode and

scan interval settings.

Normal and Remote (DI modules)

Specify Remote to use the DI module as a remote control input.

When there are multiple DI modules, only one of them can be set to Remote.

For normal DI input, specify

Normal.

When using Event action, set to

Remote.

For details on report control using event action, see page 1-108 in section 1.14, “Configuring

the Event Action Function”.

0

1

Event Action Setting

DI Record

Remote control

DI Record

DI Channel

Remote

Normal

Operation mode

DI Channel

DI input