1-4

BOP HIPWR 022108

PROGRAMMING/DISPLAY CHARACTERISTICS

Analog control Main channel (voltage or current)

–10V to +10V

Full range output, 20K Ohm input impedance
(see PAR. 3.4)

Protection Limit

channels:

+Voltage, –Voltage
+Current, –Current

+1V to +10V

10% to 100% of Nominal Range. Input voltage
clamped to 12V through 1K ohms. Maximum
of 0.15mA input current at1V input voltage.

External mode control

Voltage: open circuit or TTL logic 1
Current: short circuit or TTL logic 0

Available when activated only, or for Save/
Recall function.

External Shutdown

(see Table 2-4)

Isolated input for shutdown of the

BOP (latched status)

Pulse width: 100 microseconds min.
Action delay: 100 microseconds max
Restore operation by cycling input power or
pressing RESET key..

External Trigger

Shutdown

(see Table 2-4)

Non-isolated input for setting the

BOP in STANDBY (output off)

(latched status)

Pulse width: 100 microseconds min.
Action delay: 200 milliseconds max
Restore operation by pressing STANDBY
key. or sending OUTP ON command via
remote interface.

External Shutdown

Flag (see Table 2-4)

Isolated output indicatng

shutdown status)

Action delay: 100 microseconds max

External On-Off

Flag (see Table 2-4)

Isolated output indicatng

output on (enabled, STANDBY off) or

off (disabled, STANDBY on) status)

Action delay: 200 milliseconds max

Digital control

local

Panel-mounted keypad

Direct Entry

remote

IEEE 488-2 (GPIB)

SCPI

remote

RS 232

remote

RS 485 (BITBUS)

IEEE 1118

Display

front panel

4" backlit LCD displays all functions

remote

All parameters read back on GPIB or RS 232 buses

FUNCTION GENERATOR CHARACTERISTICS

(See PAR. 3.3.9)

Maximum number of waveforms

Local: 16

Remote: 1

Local: Saved for power-up
Remote: Lost when the unit is turned off, must
be saved on the host computer)

Maximum number of segments or basic wave-
forms per waveform

Local: 10

Remote: 126

Or maximum number of points (whichever
comes first)
• The time interval for each segment

depends on the type of waveform: period
for ramp and square waveforms, period or
fraction of period for sine and triangular
waveforms and time interval for DC levels

• Segments that cause the waveform to

exceed the maximum number of points are
not executed. For local operation they are
marked with a triple asterisk on the front
panel. For remote operation an error mes-
sage is generated.

Types of Basic waveforms

Sine (Sinusoidal waveform)

Triangle (Triangular waveform)

Pos. Ramp (Ramp waveform)

Neg. Ramp (Sawtooth waveform)

Square (50% Duty Cycle Pulse)

Level (DC waveform)

TABLE 1-2. BOP GENERAL SPECIFICATIONS (Continued)

SPECIFICATION

RATING/DESCRIPTION

CONDITION