Part A System installation and start-up Sect. 3.1

05/2002

IFC 210 E

23

3

6WDUWXS

3.1

Power-on and measurement

Before powering the system, please check that it has been correctly installed according to
Sect. 1 and 2.

The flowmeter is delivered ready for operational use. All operating data have been factory set
in accordance with your specifications.
Please refer to Sect. 3.2 “factory settings”.

Power the unit, and the flowmeter will immediately start process flow measurement.

Refer to Sect. 4 and 5 for operator control.

3.2 Factory

setting

All operating data are factory set according to your order specifications.

If you have not made any particular specifications at the time of ordering, the instruments will be
delivered with the standard parameters and functions listed in the Table below.

To facilitate easy and rapid initial start-up, current output and pulse output are set to process flow
measurement in “2 flow directions”, so that the current flowrate is displayed and the volumetric
flow counted independent of the flow direction. The measured values may possibly be shown with
a “ – ” sign.

This factory setting for the current and pulse outputs may possibly lead to measuring errors,
particularly in the case of volume flow counting:

For example, if pumps are switched off and a “backflow” occurs which is not within the range of
the low-flow cutoff (SMU), or if separate displays and counts are required for both flow directions.

To avoid faulty measurements, therefore, it may be necessary to change the factory setting of
some or all of the following functions:
– low-flow cutoff SMU, Fct. 1.03, Sect. 5.3
– display, Fct. 1.04, Sect. 5.4
– current output I, Fct. 1.05, Sect. 5.6
– pulse output P, Fct. 1.06, Sect. 5.7

Operation see Section 4 and 5.

Standard factory settings

Function Setting

Function

Setting

1.01 Full-scale

range

Q

100%

1.07

Status output B1

flow

1.02

Time constant

3 s, for I, B1, B2

directions

and display

1.08

Control input B2

off

1.03

Low-flow

ON:

1%

3.01

Language for display only

English

cutoff SMU

OFF:

2%

3.02

Flowmeter

1.04 Display

diameter

see

nameplate

flow rate

m

3

/hr or US Gal/min

flow direction (see arrow

totalizer(s)

m

3

or US Gal

on primary head)

} + direction

Messages

no

3.04

Entry

code

no

Trend

Mittelwert

3.05

User

unit

Liter/hr

or

USMGal/day

Updating

1 sec.

3.06

Application: Flow

steady

Scaling

auto

3.07

Hardware: Terminal B1

Statusoutput

1.05

Current output I

Terminal B2

Control input

function

2

directions

3.08

Location

ALTOMETER

Range

I

4-20

mA

3.09

Communication

off

I Max

22 mA

I Error

22 mA

1.06

Pulse output P

function

2 directions

pulse

width

50

ms

pulse

value

1

pulse/s