Part C Special applications, functional checks, service, and order numbers Sect. 7.6

05/2002

IFC 210 E

73


Example

Full-scale range

Q

100%

= 200 m

3

/hr (Fct. 1.01)

Meter size

DN

= 80 mm = 3” (Fct. 3.02)

Current at

Q

0%

I

0%

= 4 mA

Q

100%

I

100%

= 20 mA

}

(Fct. 1.05)

Pulses at

Q

100%

P

100%

= 200 Pulse/hr (Fct. 1.06)

Primary head constant

GK

= 3.571 (s. Geräteschild)

Constant (V

in

m

3

)

(t

in hr)

K

= 7074 (see Table)

(DN

in mm)


Calculation of „X“ and position of „Y“

Q

100%

x K

200 x 7074

X =

GK x DN

2

=

3.571 x 80 x 80

= 61.905


Y = 40, position of switch Y, see front panel GS 8A
(comes closest to X value and is smaller than X).

Calculation of setpoint readings I and f

40

I = I

0%

+ (I

100%

- I

0%

) = 4 mA +

61.905

(20mA - 4mA) = 14.3mA


Deviations are permissible between 14.1 and 14.6 mA (equivalent to ± 1.5 %)

40

f = x P

100%

=

61.905

x 200 pulses/hr = 129.2 pulses/hr


Deviations are permissible between 127.3 and 131.1 pulses/hr (equivalent to ± 1.5 %)

If you need to return your flowmeter to KROHNE,

please refer to last but one page of these Instructions !