2. In the Virtual Points section, left click on the text “Click To Add New Point”. This will create a
new row for you to enter the details of a virtual point.
3. Enter a name for the virtual point under the Name column. By default, a Virtual Point is set
to an update rate of 60 seconds. This value may be modified to any value between 5 and 300
seconds. (All actual points linked to this virtual point will be updated by iComm at this rate
or faster).
4. Click in the Name and Update Rate field to edit details, press enter when done.
Figure 3-30: New Virtual Points Created
The Virtual point may not appear in iComm until the Update rate time interval has elapsed.