Outback Power Systems VFX Series International Installation Manual User Manual

Page 38

Advertising
background image

36

FX2012ET

AC Max = 6AAC (Default = 5 AAC)

DC Max = 100ADC

FX2024ET

AC Max = 7AAC (Default = 5 AAC)

DC Max = 55ADC

FX2348ET

AC Max = 7AAC (Default = 5 AAC)

DC Max = 35ADC

VFX2612E

AC Max = 7AAC (Default = 6 AAC)

DC Max = 120ADC

VFX3024E

AC Max = 10AAC (Default = 9 AAC)

DC Max = 85ADC

VFX3048E

AC Max = 10AAC (Default = 9 AAC)

DC Max = 45ADC

AC INPUT FREQUENCY RANGE

NOTE: If the AC input source is out of the range noted below, the FX will not connect or stay connected.

All E Series FX Models

44-56 Hz

MAXIMUM AC OUTPUT CURRENT

This is the amount of surge current that the FX will quickly supply for a split second. Depending on the
size of the surge, the FX can be overloaded for a minimum time of 5 seconds to a maximum time of 30
minutes.

All 12 VDC FXs

28AAC per FX for 1 millisecond

All Other FXs

35AAC per FX for 1 millisecond/25AAC per FX for 100 milliseconds

MAXIMUM CONTINUOUS OUTPUT POWER

An FX Series Inverter/Charger’s model number indicates its maximum continuous output power by
changing the last two digits to zeros. For instance, an FX2012ET has a maximum continuous output

power of 2000VA (volt-amps).

FX2012ET

2000VA (VA = volt-Amps)

FX2024ET 2000VA

FX2348ET 2300VA

FX2612E 2600VA

VFX3024E 3000

VA

VFX3048E 3000VA

MAXIMUM AND DEFAULT AC INPUT AND DC CHARGER (bulk stage) OUTPUT VALUES

Advertising