2 auxiliary inputs, 3 digital inputs, 4 output specifications – Despatch P1400+ Temperature Controller User Manual

Page 102

Advertising
background image

96

14.2 Auxiliary Inputs

Input Sampling rate:

4 per second

Input Resolution:

13 bits minimum

Input types:

4 to 20mA, 0 to 20mA, 0 to 10V, 2 to 10V, 0 to 5V, 1 to 5V.
The Full Auxiliary input in Option Slot B also supports 0 to 100mv
and Potentiometer (2K

or higher).

Measurement Accuracy
(reference conditions):

±

0.25% of input span

±

1 LSD

Input resistance:

Voltage ranges: 47K

nominal

Current ranges: 5

Input protection:

Voltage input: will withstand up to 5x input voltage overload without
damage or degradation of performance in either polarity.

Current input: will withstand 5x input current overload in reverse
direction and up to 1A in the normal direction.

Isolation:

Slot A has basic isolation from other inputs and outputs.
Slot B has reinforced isolation from other inputs and outputs.

Sensor Break Detection:

For 4 to 20mA, 2 to 10V and 1 to 5V ranges only.

14.3 Digital Inputs

Type:

Voltage-free or TTL-compatible

Voltage-Free Operation:
functions depend on model and how
configured

Connection to contacts of external switch or relay:
Open = SP1, Automatic Mode or Local setpoint
selected. Minimum contact resistance = 5K

,

Closed = SP2, Manual Mode, Remote Setpoint
selected, Latching Relay, Stored Min/Max/Time reset
(edge triggered) or Tare activate (edge triggered).
Maximum contact resistance = 50

.

TTL levels:
functions depend on model and how
configured

2.0 to 24VDC = SP1, Automatic Mode, Local Setpoint
selected.
–0.6 to 0.8VDC = SP2, Manual Mode, Remote Setpoint
selected, Latching Relay, Stored Min/Max/Time reset
(edge triggered) or Tare activate (edge triggered).

Maximum Input Delay (OFF-ON):

0.25 second.

Maximum Input Delay (ON-OFF):

0.25 second.

Isolation:

Reinforced safety isolation from any source of
hazardous voltages.

14.4 Output Specifications

Output Module Types

Option Slot 1 Module Options:

Relay, SSR drive, Triac or DC linear.
Limit Controllers have a fixed Latching Relay only.

Option Slot 2 Module Options:

Relay, Dual Relay, SSR drive, Triac or DC linear.
Dual Relay option on some models only.

Option Slot 3 Module Options:

Relay, Dual Relay, SSR drive, DC Linear or Transmitter
PSU. Dual Relay option on some models only.

Advertising