50
Parameter
Modbus
Parameter No.
ASCII Ident &
Message Types
Notes
Controller
commands
Z
Type 3/4
R/W
Only Type 3 / 4 ASCII messages are
allowed with this parameter. The
{DATA} field must be one of eight five-
digit numbers. The commands
corresponding to the {DATA} field
value are:
00010 = Activate Manual Control
00020 = Activate Automatic Control
00030 = Activate the Self-Tune
00040 = De-activate the Self-Tune
00050 = Request Pre-Tune
00060 = Abort Pre-Tune
00130 = Activate Loop Alarm
00140 = De-activate Loop Alarm