Communications Write Enable

Type: General Definition

Enables/disables the changing of parameter values via the RS485 communications link, if the
communications option is installed. Possible settings are read only or read/write.
Display code =

CoEn

, default setting = r_

W

(read/write).

Control Type

Type: Controller Parameter

Defines if a controller has one or two control outputs. Single outputs can drive the PV in one
direction only (e.g. heat only, cool only, increase humidity etc). Dual outputs can force the PV to
increase or decrease (e.g heat & cool, humidify and dehumidify etc).
Dual control is not possible on Valve Motor Drive controllers
Display codes =

SnGL

and

duAL

, default value =

SnGL

.

Also refer to

PID

,

Primary Proportional Band

,

Process Variable

,

Secondary Proportional Band

and

Valve Motor Control

.

Controller

Type: Controller Definition

An instrument that can control a Process Variable, using either PID or On-Off control methods.
Alarm outputs are also available that will activate at preset PV values, as are other options such as
PV retransmission and Serial Communications.
Also refer to

Alarm Operation

,

Indicator

,

Limit Controller

,

On-Off Control

,

PID

,

Process Variable

,

Retransmit Output

and

Serial Communications

.

CPU

Type: General Definition

This stands for Central Processing Unit and refers to the onboard microprocessor that controls all of
the measuring, alarm and control functions of the instrument.

Current Proportioning Control

Type: Controller Definition

Current proportioning control can be implemented on units configured with linear current or voltage
output(s). It provides a 4 to 20mA, 0-20mA, 0 to 5V, 0 to 10V or 2 - 10V DC PID output. On-Off
control should not be used with Current proportioning control.
Also refer to

On-Off Control

,

PID

,

Primary Proportional Band

,

Rate

,

Secondary Proportional

Band

and

Time Proportional Control

.

Cycle Time

Type: Controller Definition

For time proportioning outputs, it is used to define time period over which the average on vs. off time
is equal to the required PID output level.

Ct1

,

Ct2

and

Ct3

are available when option slots 1, 2 or 3

are defined as time proportioning output types. The permitted range of value is 0.5, 1, 2, 4, 8, 16, 32,
64, 128, 256 or 512 seconds. Shorter cycle times will give better control, but at the expense of
reduce life when used with an electromechanical control device (e.g. relays or solenoid valves).
Display codes =

Ct1

,

Ct2

and

Ct3

, default value = 32.

Also refer to

PID

and

Time Proportioning

.

Deadband

Type: Controller Parameter

- Refer to

Overlap/Deadband

.

Derivative

Type: Controller Parameter

Refer to

Rate

.

Deviation Alarm 1 Value Type

Type: General Parameter

This is applicable only if Alarm 1 is selected to be Deviation Alarm. A positive value (Deviation High)
sets the alarm point above the current actual setpoint, a negative value (Deviation Low) sets it