Despatch P1400+ Temperature Controller User Manual

Page 57

Advertising
background image

51

Parameter

Modbus

Parameter No.

ASCII Ident &

Message Types

Notes

Bit

Meaning

0

Alarm 1 status.
0 = activated, 1 = safe

1

Alarm 2 status.
0 = activated, 1 = safe

2

Self-Tune status.
0 = disabled
1 = activated

3

Change Indicator. 1 =
A parameter other than
controller status, PV or
Output power has been
changed since the last
time the status word
was read.

4

Comms write status:
0 = disabled
1 = enabled.

5

A/M control.
0 = disabled
1 = enabled

7

Pre-tune status.
0 = disabled
1 = enabled.

Controller Status

L

Type 2

RO

8

Loop alarm status.
0 = activated, 1 = safe.

Scan Table

]

Type 2

RO

Reads back main process values.
Response is: L{N}25aaaaabbbbb
cccccdddddeeeeeA* where:
aaaaa = Actual Setpoint value
bbbbb = Process Variable value
ccccc = Primary PID Power value
ddddd = Secondary PID Power value
eeeee = Controller Status (see above)

Equipment ID

122

RO

The four digit model number 6100

Serial Number Low

123

RO

Digits aaaa

Serial Number Mid

124

RO

Digits bbbb

Serial Number High

125

RO

Digits cccc

Unit serial number.
Format aaaa bbbb
cccc, (12 BCD digits).

Date of
manufacture

126

RO

Manufacturing date code as an
encoded binary number. (e.g. 0403 for
April 2003 is returned as 193hex)