C00034/1, C00026/1, C00027/1 – Lenze E84AVSCx 8400 StateLine C User Manual
Page 38: C00010/x, Parameter description, 6commissioning

6
Commissioning
6.3
Adapting the most important parameters to the drive task
38
Lenze · 8400 StateLine · Operating instructions · from Firmware V06.00 · DMS 1.2 EN · 12/2012 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00034/1
C00026/1
C00027/1
C00010/x
Analog input (AIN1): Configuration
Configuration of the analog input for current or voltage measurement
Selection list
(Lenze setting printed in bold)
Info
0 -10...+10 V
Input signal is the voltage signal -10 V ... +10 V
• -10 V ... +10 V ≡ -100 % ... +100 %
1 0...20 mA
Input signal is the current signal 0 mA ... 20 mA
• 0 mA ... 20 mA ≡ 0 % ... +100 %
2 4...20 mA
Input signal is the current signal 4 mA ... 20 mA
• 4 mA ... 20 mA ≡ 0 % ... +100 %
• The current loop is monitored for open circuit
(I < 4 mA) by the device.
Analog input (AIN1): Offset
Setting range
(min. value | unit | max. value)
Lenze setting
-199.99
%
199.99 0.00 %
Analog input (AIN1): Gain
Setting range
(min. value | unit | max. value)
Lenze setting
-100.0000
100.0000 1.0000
Analog input (AIN1): characteristic
An individual characteristic according to the right
illustration can be parameterised for the analog input in
order to provide different slopes and a dead band. In this
case the input signal corresponds to the X axis and the
output signal corresponds to the Y axis.
Setting range
(min. value | unit | max. value)
0.00
%
199.99
Subcodes
Lenze setting
Info
C00010/1
0.00 %
AIN1: (+y0) = min
C00010/2
0.00 %
AIN1: (+x0) = Dead band
C00010/3
0.00 %
AIN1: (-y0) = (-min)
C00010/4
0.00 %
AIN1: (-x0) = (-Dead band)
C00010/5
100.00 %
AIN1: (+ymax)
C00010/6
100.00 %
AIN1: (+xmax)
C00010/7
100.00 %
AIN1: (-ymax)
C00010/8
100.00 %
AIN1: (-xmax)
199.99 %
y
max
-y
max
-x
max
x
max
y
min
-y
min
199.99 %
-199.99 %
-199.99 %