6electrical installation – Lenze E94AYCPM User Manual

Page 42

Advertising
background image

6

Electrical installation

Wiring of the PROFIBUS

EDK94AYCPM DE/EN/FR/ES/IT 6.0

42

l

H1_E_INST−Steckerleiste_Schraubanschl_15

Assignment of the Sub−D socket

View

Pin

Designation

Explanation

1

2

3
4
5

6

7
8
9

1

free

2

free

3

RxD/TxD−P

Data line B (received data/transmitted data plus)

4

RTS

Request To Send (received data/transmitted data, no
differential signal)

5

M5V2

Data ground (ground to 5V)

6

P5V2

5 V DC / 30 mA (bus termination)

7

free

8

RxD/TxD−N

Data line A (received data/transmitted data minus)

9

free