7 commissioning, Possible settings via dip switch, Commissioning 44 – Lenze E94AYCPM User Manual
Page 44: 7commissioning
![background image](/manuals/565786/44/background.png)
7
Commissioning
Possible settings via DIP switch
EDK94AYCPM DE/EN/FR/ES/IT 6.0
44
l
H1inbet−bevor
7
Commissioning
Possible settings via DIP switch
E94YCPM001D
The front panel DIP switches can be used to set
ƒ the station address (switches 1 ... 64)
ƒ compatibility with the EMF2133IB communication module (switch 2133)
Setting the station address
ƒ The station addresses for several interconnected PROFIBUS nodes have to differ from
each other.
ƒ Valid address range: 1
126 (max. 125 slave nodes)
ƒ The station address can be set via DIP switches 1 ... 64, or using the »Engineer« (code
C13899 / C14899).
Specification of the station address via ...
DIP switch
C13899 / C14899
Condition
At least one switch 1 64 = ON
All switches 1 ... 64 = OFF (Lenze
standard setting)
All switches 1 ... 64 = ON (invalid
value "127")
The labelling of the housing corresponds to the values of the individual DIP switches for
defining the station address.