Wiring, Mains choke/mains filter assignment, Electrical installation – Lenze E82EV 8200 vector 15kW-90kW User Manual
Page 140: Wiring mains choke/mains filter assignment, Operation with increased rated power, System manual

Electrical installation
Wiring
Mains choke/mains filter assignment
l
140
EDK82EV903 DE/EN/FR 5.1
5.2
Wiring
5.2.1
Mains choke/mains filter assignment
Operation at rated power on 400/500 V mains, 3/PE
8200 vector
Mains choke
Interference voltage category (EN 61800−3) and motor cable length
Component
Component
Type
Var.
Type
C2
Max. [m]
C1
Max. [m]
E82xV153K4B
2xx
ELN3−0088H035−001
EZN3A0110H030
25
EZN3B0110H030
2)
EZN3B0110H030U
3)
50
E82ZN22334B230
50
10
5)
E82ZN22334B230
10
0
5)
E82ZZ15334B230
50
10
5)
E82ZZ15334B230
10
0
5)
3xx
−
−
50
−
10
E82xV223K4B
2xx
ELN3−0075H045
EZN3A0080H042
25
EZN3B0080H042
50
E82ZN22334B230
50
10
5)
E82ZN22334B230
10
0
5)
3xx
−
−
50
−
10
E82xV303K4B
2xx
ELN3−0055H055
EZN3A0055H060
25
EZN3B0055H060
50
E82ZN30334B230
50
10
5)
E82ZN30334B230
10
0
5)
3xx
−
−
50
10
E82xV453K4B
2xx
ELN3−0038H085
EZN3A0037H090
25
EZN3B0037H090
50
E82ZN45334B230
50
10
5)
E82ZN45334B230
10
0
5)
3xx
−
−
50
10
E82xV553K4B
2xx
ELN3−0027H105
EZN3A0030H110
EZN3A0030H110N001
4)
25
EZN3B0030H110
50
E82ZN55334B230
50
10
5)
E82ZN55334B230
10
0
5)
3xx
−
−
50
−
10
E82xV753K4B
2xx
ELN3−0022H130
EZN3A0022H150
25
EZN3B0022H150
50
E82ZN75334B230
50
10
5)
E82ZN75334B230
10
0
5)
3xx
−
−
50
−
10
E82xV903K4B
2xx
ELN3−0017H170
EZN3A0017H200
25
EZN3B0017H200
50
E82ZN90334B230
50
10
5)
E82ZN90334B230
10
0
5)
3xx
−
−
50
−
10
2)
Side−mounted filter
3)
Footprint filter
4)
For E82DV553K4B (push−through technique)
5)
at switching frequency f
ch
= 16 kHz; the interference voltage category C1 cannot be achieved
Operation with increased rated power
,
System Manual