Wiring terminal strips

The supplied terminal strips are tested according to the specifications of

ƒ

DIN VDE 0627:1986−06 (partially)

ƒ

DIN EN 60999:1994−04 (partially)

Checked and tested are, for instance, mechanical, electrical and thermal load, vibration,
damage of conductors, loose conductors, corrosion, ageing.

(

Stop!

Proceed as follows to avoid damage of the terminal strip and the contacts:

ƒ

Mount or remove only when the controller is not connected to the mains!

ƒ

Wire the terminal strips before connecting them!

ƒ

Unused terminal strips must also be plugged in to protect the contacts.

8200vec015

)

Note!

Basically wiring without wire end ferrules is possible.
If safety functions (e.g. "Safe torque off") are used, insulated wire end ferrules
or rigid conductors are required!

5.2.3

EMC−compliant wiring

(Design of a CE−typical drive system)

)

Note!

ƒ

Control cables and mains cables must be separated from the motor cable to
avoid interferences.

ƒ

Control cable must always be shielded.

ƒ

We recommend to shield the supply cable for the PTC or thermal contact
and route it separately from the motor cable.