C00074 | reset time imax/m controller, C00075 | vp current controller, C00076 | ti current controller – Lenze 8400 TopLine User Manual
Page 902: C00077 | sc: vp field controller, C00075, C00076, C00077, Ller, C00074/1, C00074

17
Parameter reference
17.2
Parameter list | C00074
902
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00074
C00075
C00076
C00077
Parameter | Name:
C00074 | Reset time Imax/M controller
Data type: UNSIGNED_16
Index: 24501
d
= 5FB5
h
Reset time Ti of certain controllers for different motor control modes
Setting range
(min. value | unit | max. value)
0
ms
9990
Subcodes
Lenze setting
Info
C00074/1
65 ms
: Ti Imax controller
C00074/2
30 ms
: Ti torque controller
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00075 | Vp current controller
Data type: UNSIGNED_16
Index: 24500
d
= 5FB4
h
Gain factor Vp of the current controller for servo control (
) and certain inverter functions (parameter
identification, flying restart circuit)
• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically.
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
V/A
500.00 7.00 V/A
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00076 | Ti current controller
Data type: UNSIGNED_16
Index: 24499
d
= 5FB3
h
Reset time Ti of the current controller for servo control (
) and certain inverter functions (parameter identification,
flying restart circuit)
• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically.
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
ms
500.00 10.61 ms
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00077 | SC: Vp field controller
Data type: UNSIGNED_16
Index: 24498
d
= 5FB2
h
Gain factor Vp of the field controller for servo control (
• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically.
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
500.00 12.80
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100