Valid Keepers and Signatures
This example shows a Keeper Status dialog box where the ControlNet network
that is comprised of valid keepers and signatures.
Valid Keeper Status and Signatures
Unconfigured Keeper
The example below shows the Keeper Status dialog box where a module has an
unconfigured status. Besides the status shown, the module status display indicates
Keeper: Unconfigured (node address changed).
This error results when the module’s node address has been changed. After
changing the node address, the module was used as a replacement and inserted
into the redundant chassis.
Figure 63 - Keeper Status - Unconfigured
To correct this anomaly, do one of the following:
• Select the unconfigured module and click Update Keeper.
• Reschedule the ControlNet network.