Chapter 3

Install the Enhanced Redundancy System

Figure 13 - 1756-RM/A or RM/B and 1756-RMXT Modules

To install the redundancy module, follow these steps.

1. Align the circuit board with top and bottom guides in the chassis.
2. Slide the module into the chassis, making sure the module backplane

connector properly connects to the chassis backplane.

The module is properly installed when it is flush with other installed modules.

This completes the installation of the first chassis and its components. Chassis

power must remain off.

Redundancy Module

PRI COM OK

31941-M

44487

LC Single-

mode

Connector

1756-RM/A or 1756-RM/B Module

1756-RMXT Module

Front View

Backplane

Connector

Bottom View

Backplane

Connector

Front View

Top View

Top View

Bottom View

Side View

Side View

Status Indicators

Status Indicators

LC Single-

mode

Connector

IMPORTANT

To remove the module, push on the locking clips at the top and bottom of each
module and slide the module out of the chassis.

IMPORTANT

If you are adding redundancy to an already operational ControlLogix system,
shut off your process to install the redundancy module. The first chassis you

install the redundancy module into and turn on, becomes the primary chassis.
You can also have to do the following:
Use RSNetWorx software to configure keeper information in the secondary

ControlNet communication module if the master keeper for ControlNet

communication is in the primary chassis

Enable redundancy in RSLogix 5000 software and remove any I/O modules

from the chassis