Communicate with ASCII Devices Chapter 21
For example, this string requests the first two variables from the slave.
ASCII Slave - Controller Response
If the controller receives a request from an ASCII master, it responds
in this format (each character is one byte).
Start Sign
Destination
Source
Function Code
Start Address
Number of
Variables
End Sign
^
15
01
R
00000
002
&
Start Sign
Destination
Source
Function
Code
Start
Address
Number of
Variables
Number of
Characters
Data
End Sign
1 char
2 char
2 char
1 char
5 char
3 char
4 char
maximum
10000 char
1 char
Component
Description
Start Sign
identifies the start of a message
^ character
Destination
unique master address (requester)
01…99
Source
unique slave address (GuardPLC controller)
01…99
Function Code
r character identifies data sent by slave
E identifies error with master request
Start Address
data start address for characters to read (offset)
00000…65535
Number of Variables
number of variables to read and send back to master
000…999
Number of Characters
number of characters in the data string (This includes
the “/” delimiter but not the “&” termination character.)
0000…9999
Data
data characters
End Sign
needed to recognize the end of a message
& character
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems