Analog input signals for 1753-if8xof4 modules – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 323

Publication 1753-UM001C-EN-P - March 2010
323
System Signal Variables Appendix B
Analog Input Signals for 1753-IF8XOF4 Modules
The 1753-IF8XOF4 module supports these analog input signals.
I/O Data
Read/Write
Description
Module.SRS
Read
Slot number (System.Rack.Slot)
Module.Type
Read
Module type: 0x001E
Module.Error.Code
Read
Error mask for the module
0x0000
I/O processing may be running with errors
0x0001
No I/O processing (CPU not in RUN)
0x0002
No I/O processing during start-up tests
0x0004
Manufacturing interface running
0x0010
No I/O processing due to incorrect configuration
0x0020
No I/O processing due to exceeded fault rate
0x0040/80
No I/O processing because configured module is not plugged in
AI.Error Code
Read
Error mask for all analog inputs
0x0001
Module error
0x0004
MEZ test, time monitoring of conversion
0x0008
FTZ test: walking bit of data bus faulty
0x0010
FTZ test: Operating voltages faulty
0x0020
MEZ test, active disconnection failed
0x0040
A/D conversion faulty
0x0080
MEZ test: cross links of MUX faulty
0x0100
MEZ test: walking bit of data bus faulty
0x0200
MEZ test: multiplexer addresses faulty
0x0400
MEZ test: operating voltages faulty
0x0800
MEZ test: measuring system (characteristic) faulty (unipolar)
0x1000
MEZ test: measuring system (final values, zero point) faulty
(unipolar)
0x8000
A/D conversion faulty (DRDY_HIGH)
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems